2
Hardwiring
Wiring must be performed by a qualified electrician.
1.
Install a utility circuit breaker in accordance with local electrical codes (see tables below) for
input wiring only.
2.
Switch the UPS input circuit breaker and utility circuit breakers OFF.
3.
Remove the access panel.
4.
Remove circular knockouts.
5.
Run wires through access panel to terminal blocks. Wire to ground block first.
Adhere to all
national and local electrical codes.
6.
Use appropriate glands to achieve strain -relief on the hardwired input and output power cables.
Input Connection
Output Connection (optional)
Wire to L1, L2,
Wire to L1A, L2A,
System
Wiring
Voltage
Current
Full Load
(Nominal)
External Input
Circuit Breaker
(typical)
Wire Size
(typical)
1609-P8000E
Input & Output
208/2 30 V
40 A
XLTW
- 38 A
50 A / 2-pole for
Input Wiring Only
Allen-Bradley
Catalog Number
1492-MCAA2H50
# 8 AWG/
10mm
2
1609-P10000E
Input & Output
208/2 30 V
54 A
XLTW
-50 A
70 A / 2-pole for
Input Wiring only
Allen-Bradley
Catalog Number
1492-MCBA2H70
# 6 AWG/
16mm
2
7.
Switch the circuit breakers ON.
8.
Check line voltages.
9.
Replace the access panel.