background image

 

8

 

U

SER 

C

ONFIGURABLE 

I

TEMS

 

N

OTE

:

  

S

ETTINGS ARE MADE THROUGH SUPPLIED 

P

OWER

C

HUTE SOFTWARE

,

 

 

OPTIONAL 

N

ETWORK 

M

ANAGEMENT CARDS

,

 OR 

T

ERMINAL 

M

ODE

F

UNCTION

 

F

ACTORY

 

D

EFAULT

 

U

SER 

S

ELEC TABLE 

C

HOICES

 

D

ESCRIPTION

 

Automatic Self-Test 

Every 14 days  
(336 hours) 

Every 7 days  
(168 hours), 
Every 14 days  
(336 hours), 
On Startup Only,  
No Self-Test 

Set the interval at which the 
UPS will execute a self-test. 

UPS ID 

UPS_IDEN 

Up to eight characters to 
define the UPS 

Uniquely identify the UPS, (i.e. 
server name or location) for 
network management purposes. 

Date of Last Battery 
Replacement 

Manufacture Date 

mm/dd/yy 

Reset this date when you replace 
the battery modules. 

Minimum Capacity 
Before Return from 
Shutdown 

0 percent 

0, 15, 25, 35, 50, 60, 75,  
90 percent 

Specify the percentage to which 
batteries will be charged 
following a low-battery 
shutdown before powering 
connected equipment. 

Alarm Delay After  
Line Failure 

5 second delay 

5 second delay,  
30 second delay, 
At Low Battery, 
Never 

Mute ongoing alarms or disable 
all alarms permanently. 

Shutdown Delay 

20 seconds 

0, 20, 60, 120, 240, 480, 
720, 960 seconds 

Set the interval between the time 
when the UPS receives a 
shutdown command and the 
actual shutdown. 

Duration of  
Low Battery Warning. 

 

2 minutes 

PowerChute 
software provides 
automatic, 
unattended 
shutdown when 
approximately two 
minutes of battery 
runtime remains. 

2, 5, 7, 10, 12, 15, 18,  
20 minutes. 

The low battery warning beeps 
become continuous when two 
minutes of runtime remains. 

Change the warning interval to a 
higher setting if the operating 
system requires a longer interval 
for shutdown. 

Synchronized Turn-on 
Delay 

0 seconds 

0, 20, 60, 120, 240, 480, 
720, 960 seconds 

Specify the time the UPS will 
wait after the return of utility 
power before turn-on (to avoid 
branch circuit overloads).  

High Bypass Point 

 

+10% of  
output voltage 
setting 

+5%, +10%, +15%, 
+20% 

Maximum voltage that the UPS 
will pass to connected 
equipment during internal 
bypass operation. 

Summary of Contents for 1609-P10000E

Page 1: ...41063 261 01 1 990 2672 09 2005 Allen Bradley User Manual for 8000 10000 VA UPS 1609 P8000E 8000 VA 200 240 VAC 1609 P10000E 10000 VA 200240 VAC Tower Rack Mount 6U Uninterruptible Power Supply...

Page 2: ...rt Guide Removing the Batteries The unit is heavy To lighten the unit remove the batteries Refer to the unpacking instructions on the carton in which the unit is shipped Environmental Specifications T...

Page 3: ...6 Use appropriate glands to achieve strain relief on the hardwired input and output power cables Input Connection Output Connection optional Wire to L1 L2 Wire to L1A L2A System Wiring Voltage Current...

Page 4: ...3 Installing and Connecting the Batteries and Attaching the Front Bezel...

Page 5: ...up the UPS The battery charges to 90 capacity during the first three hours of normal operation Do not expect full battery run capability during this initial charge period OPTIONS q External Battery Pa...

Page 6: ...ely de energized from a remote location without switching to battery operation see EPO Option TVSS Screw The UPS features a transient voltage surge suppression TVSS screw for connecting the ground lea...

Page 7: ...ch Battery operation is not available while the UPS is in bypass mode see Troubleshooting Fault The UPS detects an internal fault see Troubleshooting Overload The connected loads are drawing more powe...

Page 8: ...ltage display Press and hold the button to view the utility voltage bar graph display After a few seconds the five LED Battery Charge display on the right of the front panel shows the utility input vo...

Page 9: ...nt Alarm Delay After Line Failure 5 second delay 5 second delay 30 second delay At Low Battery Never Mute ongoing alarms or disable all alarms permanently Shutdown Delay 20 seconds 0 20 60 120 240 480...

Page 10: ...bypass operation Output Voltage 208 230 V models 230 VAC 208 230 V models 200 208 220 230 240 VAC Allows the user to select the UPS output voltage while online Output Frequency Automatic 50 3 Hz or 6...

Page 11: ...uit UL CSA standards and an SELV circuit IEC standard Both Class 2 and SELV circuits must be isolated from all primary circuitry Do not connect any circuit to the EPO terminal block unless it can be c...

Page 12: ...nal battery packs Once the blank terminal window is open follow these steps to enter the number of battery packs Press ENTER to initiate terminal mode Press ENTER multiple times until the prompt User...

Page 13: ...outages Use caution when handling heavy battery modules Refer to Installing and Connecting the Batteries and Attaching the Front Bezel for battery replacement procedure reverse instructions for batte...

Page 14: ...or are near the end of service life Charge the battery module s Modules require recharging after extended outages and wear faster when put into service often or when operated at elevated temperatures...

Page 15: ...he battery connectors are fully engaged Weak battery Allow the battery to recharge for 24 hours Then perform a self test If the problem persists after recharging replace the battery Failure of a batte...

Page 16: ...Support Refer to Contact Information below 3 Pack the UPS in its original packaging Pack the UPS properly to avoid damage in transit Never use Styrofoam beads for packaging Damage sustained in transi...

Page 17: ...N Deenergizing Safety If the UPS has an internal energy source battery the output may be energized when the unit is not connected to a utility power outlet To deenergize a pluggable UPS press the OFF...

Reviews: