Rockwell Automation Publication 1718-UM001A-EN-E - December 2019
33
Appendix
B
Technical Data
Power Supply
Rated voltage: 24V DC
Use a suitable power supply to implement another supply voltage of 24V DC.
The maximum permitted supply voltage for an upstream power supply is
253V AC.
Power consumption:
•
Max. 30 W for
Zone 2
(how bout for Zone 1?)
applications
•
Max. 45 W for application in safe area
Mechanical Data
Weight:
•
Backplane 1718-A20:
Approx. xxxx g (xx.x oz)
•
Backplane 1718-A10:
Approx. xxxx g (xx.x oz)
Dimensions:
•
Backplanes: See
Design and Dimensions on page 20
•
Single-width I/O modules: 16 x 100 x 103 mm (0.63 x 3.94 x 4.06 in.)
•
Dual-width I/O modules: 32 x 100 x 103 mm (1.26 x 3.94 x 4.06 in.)
•
Adapters and power supplies: 32 x 100 x 103 mm (1.26 x 3.94 x 4.06 in.)
Topic
Page
ATTENTION:
Damage to equipment
Equipment can be damaged by voltages that are too high, for example, in
temporary faulty operation.
Ensure that the supply voltage of the power supplies used in Zone 2 does not
exceed 33.6V DC (24V x 1.4).