Publication 1747-UM005B-EN-P - March 2006
6-18
Module Configuration Using the Backplane
Reset the Interface Module
from the SLC Processor
The SLC processor can perform a soft reset of the interface module
when the module is in either software Run or software Configuration
mode. If the Reset bit is set, all other configuration information within
that Output Image file will be ignored by the interface module. The
reset is accomplished as listed below.
Reset the Module from the SLC Processor
With the SLC processor you
The interface module then
1. Set the Reset Interface Module
Bit (O:e.0/12).
2. Performs a reset.
3. Sets the Reset Acknowledgement
Bit (I:e.0/12) if the module detects
the Reset bit is high. Otherwise,
the module will assume a normal
power cycle reset occurred and
will not need to set the Reset
Acknowledgement bit.
4. Reset the Reset Interface Module
Bit (O:e.0/12).
5. Resets the Reset
Acknowledgement Bit (I:e.0/12).
Summary of Contents for 1747-KE
Page 1: ...DH 485 RS 232C Interface Module Catalog Number 1747 KE User Manual AB Parts ...
Page 4: ...Publication 1747 UM005B EN P March 2006 2 Summary of Changes Notes ...
Page 12: ...Publication 1747 UM005B EN P March 2006 4 Preface ...
Page 26: ...Publication 1747 UM005B EN P March 2006 2 4 Quick Start ...
Page 88: ...Publication 1747 UM005B EN P March 2006 7 4 Interpret the LED Indicators ...
Page 116: ...Publication 1747 UM005B EN P March 2006 8 28 Application Examples ...
Page 120: ...Publication 1747 UM005B EN P March 2006 A 4 Specifications ...
Page 130: ...Publication 1747 UM005B EN P March 2006 C 6 Lithium Battery Replacement Handling and Disposal ...
Page 134: ...Publication 1747 UM005B EN P March 2006 D 4 Interface Module Configuration Worksheets ...
Page 138: ......