Publication 1747-UM005B-EN-P - March 2006
5-6
Module Configuration Using an ASCII Terminal
DF1 Port Menu
The DF1 PORT Setup Menu provides five selections.
DF1 PORT Setup Menu
DF1 Port Setup Parameters
When the module is powered up for the first time, the DF1 port will
be set to the default parameters. If these parameters are changed and
the setup is saved, then the module will always power up with the
new settings, unless the battery fails and power to the module’s RAM
is lost.
DF1 Port Setup Parameters
DF1 POR
T Setup Menu
1. Baudrate
2. Bits per character
3. Parity
4. Stop bits
X. SAVE AND EXIT
Enter Selection. . . . .
Parameter
Default
Options
Description
Communication Rate 1200
300, 600, 1200, 2400,
4800, 9600, 19200
The speed in bits per second at which data is transferred.
Must be set the same as the DF1 device.
Bits Per Character
8
7, 8
The size in number of bits of each character to be
transferred. Must be set the same as the DF1 device.
Parity
None
Even, Odd, None
Used for checking data during the transfer. Must be set the
same as the DF1 device.
Stop Bits
1
1, 2
Used for delineating data during the transfer. Must be set
the same as the DF1 device.
Summary of Contents for 1747-KE
Page 1: ...DH 485 RS 232C Interface Module Catalog Number 1747 KE User Manual AB Parts ...
Page 4: ...Publication 1747 UM005B EN P March 2006 2 Summary of Changes Notes ...
Page 12: ...Publication 1747 UM005B EN P March 2006 4 Preface ...
Page 26: ...Publication 1747 UM005B EN P March 2006 2 4 Quick Start ...
Page 88: ...Publication 1747 UM005B EN P March 2006 7 4 Interpret the LED Indicators ...
Page 116: ...Publication 1747 UM005B EN P March 2006 8 28 Application Examples ...
Page 120: ...Publication 1747 UM005B EN P March 2006 A 4 Specifications ...
Page 130: ...Publication 1747 UM005B EN P March 2006 C 6 Lithium Battery Replacement Handling and Disposal ...
Page 134: ...Publication 1747 UM005B EN P March 2006 D 4 Interface Module Configuration Worksheets ...
Page 138: ......