Rockwell Automation Publication 1756-IN061B-EN-P - February 2017
5
Armor ControlLogix Controllers
Install the Armor ControlLogix Controller
The controller ships with the power switch inside the enclosure set to ON and the controller in Remote Program mode. You can make power
connections and EtherNet/IP network connections without opening the access door on the enclosure. However, if you need to access the power
switch, USB port, memory card, or key, you must open the enclosure access door.
Follow these steps, described in this publication, to install the controller.
1.
Mount the Controller
2.
Ground the Controller
3.
Open the Access Door
, optional
4.
Remove and Install the Memory Card
, optional
5.
Connect to the USB Port
, optional
6.
Make Network Connections
7.
Make Power Connections
8.
Set the Network IP Address of the EtherNet/IP Modules
9.
Update the Controller
Mount the Controller
Observe these minimum spacing requirements around the enclosure.
Mounting feet can be attached in either horizontal or vertical orientation as shown in
Product Dimensions on page 6
. Attach the mounting feet to
the enclosure by using the four flat-head screws that are supplied with the mounting feet. Torque screws to 8.5 N•m (75.2 lb•in).
Mount the module directly to a machine by using four mounting holes. The mounting hole diameter is 6.8 mm (0.27 in.) on the mounting feet that
are included with the enclosure. Use four M6 screws and torque screws to 6.6 N•m (58 lb•in). See the
Product Dimensions on page 6
.
ATTENTION:
Make sure that all connectors and caps are securely tightened to seal connections properly against leaks and maintain IP67 requirements.
30 mm (1.18 in.)
30 mm (1.18 in.)
30 mm (1.18 in.)
30 mm (1.18 in.)