41053-363-01
DIR 41053-363
(Version 04)
(5)
Multiple of FLA
Intensités pleine charge multiples
Múltiplo de FLA
Vielfache des FLA-Wertes
Intensités pleine charge multiples
Multiplo di Max amp.
Class 10
Class 15
Class 20
Class 30
Trip Curve
HOT START
DEMARRAGE A CHAUD
WARMSTART
ARRANQUE EN CALIENTE
PARTIDA À QUENTE
AVVIAMENTO A CALDO
COLD START
DEMARRAGE A FROID
KALTSTART
ARRANQUE EN FRIO
PARTIDA À FRIO
AVVIAMENTO A FREDDO
Courbe de déclenchement
Auslösekurve
Curva del disparo
Curva de disparo
Curva di intervento
0.1
1
10
100
1000
0.1
1
10
100
1000
0.1
1
10
100
1000
1
8
8
0.1
1
10
100
1000
1
1
8
8
1
Table 1 Standard Fault Short Circuit Ratings per UL508 and CSA 22.2 No.14
Max. available fault
current (kA)
Max. voltage (V)
193, 193R
EEGF
10
600
E1 Plus Cat. No.
Short Circuit Ratings
Fuse Coordination
Table 2 High Fault Short Circuit Ratings per UL508 and CSA 22.2 No.14
Contactor Cat. No.
Max. starter FLC
(A)
Max.available
fault current (kA)
Max. voltage (V)
Max. UL Class J or CC,
CSA HRCI-J fuse (A)
193, 193R
EEGF
100-D95
90
100
600
200
E1 Plus Cat. No.
Table 3 IEC Short Circuit Ratings per EN60947-4-1
Prospective S.C.
current, Ir (kA)
Conditional S.C.
current, Iq (kA)
Max. voltage (V)
193, 193R
EEGF
5
100
600
E1 Plus Cat. No.
Table 1 IEC Type I and Type II Fuse Coordination with Bul. 100-C contactors per EN60947-4-1
Contactor Cat. No.
Max. starter FLC
(A)
Prospective S.C.
current, Ir (kA)
Conditional S.C.
current, Iq (kA)
Max. voltage
(V)
Type I with Max.
Class J fuse (A)
Type II with Max.
Class J fuse (A)
193, 193R
EEGF
100-D95
90
5
100
600
200
200
E1 Plus Cat. No.