Install the PanelView 5500 Terminal
Chapter 2
Mounting Considerations
Consider the following when mounting the terminal:
•
Mount the terminal at a height suitable for operators. You can mount the
cabinet at a level other than the operator floor.
•
Use appropriate light. Do not operate the terminal in direct sunlight.
•
Terminals are rated to operate at mounting angles between 0…180 degrees.
Figure 3 - Acceptable and Unacceptable Mounting Positions
Mounting Clearances
Plan for adequate space around the terminal, inside the enclosure, for ventilation
and cables. Consider the heat from other devices in the enclosure. The ambient
temperature around the terminal must be 0…55 °C (32…131 °F).
ATTENTION:
Failure to follow these guidelines can result in personal injury or
damage to the panel components.
1
6
6
6
1
1
1
6
6
6
1
1
1
6
6
6
1
1
Acceptable
Unacceptable
≤ 90°
From Vertical
≤ 90°
From Vertical
Table 10 - Minimum Required Clearances
Product Area
Minimum Clearance
Top
51 mm (2 in.)
Bottom
102 mm (4 in.)
Side
25 mm (1 in.)
102 mm (4 in.) is required to insert and remove an SD card or cable on one side
Back
0 mm (0 in.)
Summary of Contents for 2715-15CA
Page 6: ...6 Rockwell Automation Publication 2715 UM001A EN P July 2015 Table of Contents Notes...
Page 16: ...16 Rockwell Automation Publication 2715 UM001A EN P July 2015 Chapter 1 Overview Notes...
Page 88: ...88 Rockwell Automation Publication 2715 UM001A EN P July 2015 Chapter 6 Update Firmware Notes...
Page 104: ...104 Rockwell Automation Publication 2715 UM001A EN P July 2015 Index...
Page 105: ......