22
Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
Chapter 2
Install the PanelView 5500 Terminal
Panel Guidelines
The terminals are panel-mounted devices that mount in the door or wall of a
NEMA, UL Type, or IP rated enclosure:
•
Enclosure panels must meet the panel thickness requirements in
•
The material strength and stiffness of the panel must be sufficient to hold
the terminal and maintain an appropriate seal against water and dust.
•
The panel surface must be flat and free of imperfections to maintain an
adequate seal and NEMA, UL Type, or IP ratings.
Panel Cutout Dimensions
Use the template that is shipped with your terminal to mark the cutout
dimensions.
Table 11 - PanelView 5500 - Panel Cutout Dimensions
Terminal Size
Input Type
Height, mm (in.)
Width, mm (in.)
6.5-in.
Keypad and touch
142 (5.59)
237 (9.33)
Touch
142 (5.59)
184 (7.24)
9-in.
Touch
162 (6.38)
252 (9.92)
10.4-in.
Keypad and touch
224 (8.82)
335 (13.19)
Touch 224
(8.82)
269
(10.59)
12.1-in.
Touch
218 (8.58)
312 (12.28)
15-in.
Keypad and touch
290 (11.42)
418 (16.46)
Touch
290 (11.42)
353 (13.90)
19-in.
Touch
383 (15.08)
457 (17.99)
Summary of Contents for 2715-15CA
Page 6: ...6 Rockwell Automation Publication 2715 UM001A EN P July 2015 Table of Contents Notes...
Page 16: ...16 Rockwell Automation Publication 2715 UM001A EN P July 2015 Chapter 1 Overview Notes...
Page 88: ...88 Rockwell Automation Publication 2715 UM001A EN P July 2015 Chapter 6 Update Firmware Notes...
Page 104: ...104 Rockwell Automation Publication 2715 UM001A EN P July 2015 Index...
Page 105: ......