Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
33
Install the PanelView 5500 Terminal
Chapter 2
Connect to AC Power
Terminals with an AC power supply have these power ratings:
•
100…240V AC (50…60 Hz)
•
105VA maximum
To connect the operator terminal to an AC power source, follow these steps.
1.
Verify that the wiring is not connected to a power source.
2.
Strip 7 mm (0.28 in.) of insulation from the ends of the wire.
3.
Secure the AC power wires to the marked terminals (L1 and L2N) on the
terminal block.
4.
Secure the protective earth ground wire to the marked terminal on the
terminal block.
The protective earth terminal must be connected to a low-impedance
earth ground.
5.
Apply power to the operator terminal.
ATTENTION:
Improper wiring of the power terminals can result in voltage at
the communication connector shells.
Do not apply power to the terminal until all wiring connections have been made.
Failure to do so can result in electrical shock.
ATTENTION:
The earth ground connection to ground is mandatory. This
connection is required for noise immunity, reliability, and
Electromagnetic Compliance (EMC) with the European Union (EU) EMC
Directive for CE-mark conformance. This connection is required for
safety by Underwriters Laboratory (UL).
7 mm
20 mm
1
1
L1
L2/Neutral
Protective Earth
to Ground Bus
Summary of Contents for 2715-15CA
Page 6: ...6 Rockwell Automation Publication 2715 UM001A EN P July 2015 Table of Contents Notes...
Page 16: ...16 Rockwell Automation Publication 2715 UM001A EN P July 2015 Chapter 1 Overview Notes...
Page 88: ...88 Rockwell Automation Publication 2715 UM001A EN P July 2015 Chapter 6 Update Firmware Notes...
Page 104: ...104 Rockwell Automation Publication 2715 UM001A EN P July 2015 Index...
Page 105: ......