Rockwell Automation Publication 2715-UM001A-EN-P - July 2015
55
Configure Terminal Settings
Chapter 3
Calibrate the Touch Screen
The touch screen is calibrated at the factory. After installation, you can
recalibrate the touch screen to compensate for parallax if the screen is viewed at
an angle.
The calibration process requires you to touch a series of targets on the screen.
To calibrate the touch screen, follow these steps.
1.
Press the navigation button on the terminal.
2.
Tap Settings, or tab to the menu item and press Enter.
3.
Tap Display.
4.
Tap Calibrate Touch.
A red target appears on the screen.
5.
Press and hold the center of the target until the target completes the circle.
The next target appears.
IMPORTANT
For accuracy and to prevent damage to the touch screen, use a plastic stylus
device with a minimum tip radius of 1.3 mm (0.051 in.).
TIP
Touch inside the target areas before the progress indicator completes a circle.