Rockwell Automation Publication 825-UM004D-EN-P - November 2012
119
825-PDN DeviceNet Communication Card
Chapter
9
2.
Set the data rate switches.
Table 54 - Data Rate Setting
3.
Cycle power to the card to initialize the new settings.
Using RSNetWorx for DeviceNet
Follow these steps if the hardware switches are left in the factory default settings
or in the range of 64…99 for the node address and 3…9 for the data rate. To begin
the configuration of the 825-P Modular Protection System using software,
execute the RSNetWorx software and complete the following procedure. You
must use RSNetWorx Revision 3.21 Service Pack 2 or later.
1.
After going on-line using RSNetWorx for DeviceNet, do the following:
•
Select the
Network
menu.
•
Select
Online
.
2.
Choose the appropriate DeviceNet PC interface. In this example, a
1784-PCIDS module is chosen. Other common DeviceNet interfaces
are the 1770-KFD, and 1784-PCD.
3.
Select
OK
.
4.
RSNetWorx notifies the user to upload or download devices before
viewing configuration. Select
OK
.
5.
RSNetWorx now browses the network and displays all of the nodes it has
detected on the network. For some versions of RSNetWorx software, the
825-P Modular Protection System EDS files and icon might not be
included, and the device could be identified as an unregistered device.
If the screen appears like in Figure 42, continue with Registering
an EDS file.
Switch Setting
Description
0
125 K
1
250 K
2
500 K
3…9
For a switch setting in this range, data rate setting is determined by the
software setting using the RSNetWorx for DeviceNet configuration tool.
Note:
The card is factory default set to autobaud to the network data rate.
9
Factory default setting.
NOTE:
DeviceNet drivers must be configured using RSLinx prior to being available to RSNetWorx.
Summary of Contents for 825-P
Page 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Page 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Page 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Page 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Page 265: ......