Rockwell Automation Publication 825-UM004D-EN-P - November 2012
173
ASCII Serial Communications
Chapter
12
SHOW
Use the
SHOW
command to view relay settings and serial port settings (see
SHOW
command options are listed in Table 104.
You can append a setting name to each of the commands to specify the first
setting to display (e.g.,
SHO 50P1P
displays the relay settings starting with
setting 50P1P). The default is the first setting.
The
SHOW
command displays only the enabled settings. To display all the
settings, including disabled/hidden settings, append an
A
to the
SHOW
command (e.g.,
SHOW A
).
n
is M to enter I/O mapping settings.
s
is the short parameter name of the specific setting you want to jump to and begin setting.
If
s
is not entered, the relay starts at the first setting (e.g., enter 50PIP to start at Short Circuit Trip
level setting).
TERSE
instructs the relay to skip the settings display after the last setting.
Use this parameter to speed up the SET command.
If you want to review the settings before saving, do not use the TERSE option.
Table 104 - SHOW Command Options
Command
Description
SHOW
Show relay settings.
SHO A
Show all relay settings: enabled, disabled/hidden.
SHO P
Show serial port settings.
SHO M
Show I/O mapping settings.
Table 103 - SET Command Format
SET n s TERSE
Summary of Contents for 825-P
Page 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Page 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Page 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Page 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Page 265: ......