Rockwell Automation Publication 825-UM004D-EN-P - April 2012
209
Parameter List
Chapter
B
Freq
Settings
271
40172
400172
FREQ1 TRIP ENABL
0 = N
0
—
—
Get/Set
1 = Y
272
40173
400173
FREQ1 TRIP LEVEL
450
650
600
10
Hz
Get/Set
273
40174
400174
FREQ1 TRIP DELAY
0
2400
10
10
s
Get/Set
274
40175
400175
FREQ1 WARN ENABL
0 = N
0
—
—
Get/Set
1 = Y
275
40176
400176
FREQ1 WARN LEVEL
450
650
600
10
Hz
Get/Set
276
40177
400177
FREQ1 WARN DELAY
0
2400
10
10
s
Get/Set
277
40178
400178
FREQ2 TRIP ENABL
0 = N
0
—
—
Get/Set
1 = Y
278
40179
400179
FREQ2 TRIP LEVEL
450
650
600
10
Hz
Get/Set
279
40180
400180
FREQ2 TRIP DELAY
0
2400
10
10
s
Get/Set
280
40181
400181
FREQ2 WARN ENABL
0 = N
0
—
—
Get/Set
1 = Y
281
40182
400182
FREQ2 WARN LEVEL
450
650
600
10
Hz
Get/Set
282
40183
400183
FREQ2 WARN DELAY
0
2400
10
10
s
Get/Set
Load
Control Set
283
40184
400184
LOAD CONTROL SEL
0 = Off
0
—
—
Get/Set
1 = Current
2 = Power
3 = TCU
284
40185
400185
LD CTL UPP ENABL
0 = N
0
—
—
Get/Set
1 = Y
285
40186
400186
LD CTL CUR UPPER
20
200
50
10
x Ie
Get/Set
286
40187
400187
LD CTL PWR UPPER
1
25000
22500
1
kW
Get/Set
287
40188
400188
LD CTL TCU UPPER
1
99
90
1
%TCU
Get/Set
288
40189
400189
LD CTL LOW ENABL
0 = N
0
—
—
Get/Set
1 = Y
289
40190
400190
LD CTL CUR LOWER
20
200
50
10
x Ie
Get/Set
290
40191
400191
LD CTL PWR LOWER
1
25000
12500
1
kW
Get/Set
291
40192
400192
LD CTL TCU LOWER
1
99
90
1
%TCU
Get/Set
Group
DeviceNet
Param No.
Modbus Register
Parameter Name
Min
Max
Default
Scale
Factor
Units
Access
Read (0x03h)
Write (0x06h)
Summary of Contents for 825-P
Page 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Page 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Page 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Page 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Page 265: ......