28
Rockwell Automation Publication 825-UM004D-EN-P - November 2012
Chapter 2
Installation
Full-Voltage Reversing Starter
Full-voltage reversing starter motor applications require the following settings:
•
TWO SPEED ENABLE = Y (Yes)
•
IN1 = 0 0 0 0 0 0 0 1 0 0 (Speed 2)
•
FVR PHASING = the phase (A, B, or C) that is not changing
•
CT RATIO-2nd = CT RATIO
•
MOTOR FLA-2nd = MOTOR FLA
•
MOTOR LRC-2nd = MOTOR LRC
•
MOTOR LRT-2nd = LOCKED ROTOR TIME
•
ACCEL FACT-2nd = ACCEL FACTOR
•
RUN ST TC-2nd = RUN STATE TIME K
Figure 17 - AC Connections for Full-voltage Reversing Starter
Star-Delta Starting
The star-delta application in the following figures requires the following auxiliary
relay settings:
•
AUX#H = 0001000 (Star), AUX# FAIL-SAFE = N
•
AUX#H = 0000100 (Delta), AUX# FAIL-SAFE = N
825-P
825-MCM
L3
L2
L1
1
3
5
6
4
2
M
3 ~
Converter Module
825-MCM2
825-MCM5
825-MCM20
825-MCM180
825-MCM420
825-MCM630N
(I)
(II)
825-P
Y12 Y1-
+ -
24V AC/V DC
L
N