Hardware Commissioning
Chapter
4
Adding the Optional
Communication Card
•
Remove control power from the relay, and remove the back cover
•
Add the optional communication card into Slot C in the 825-P
•
Replace the cover and reapply control power to the relay
•
Navigate to Main > Status to view the Status display
•
If the display shows the following message:
•
Press the Enter key to confirm that you want this hardware change
•
Select Yes to confirm the new hardware configuration, and the display
will show:
•
Press Enter to reboot the relay
•
If there is an address conflict on the internal communication bus, the
display show the following message:
•
To correct this conflict, navigate to Main > Set/Show > Port > Port 4
and select the parameter named “Modbus Slave ID”
•
Change the Modbus Slave ID to the value of 247
•
Press the ESC key, and the display will show the following message:
•
Select Yes to resolve the address conflict
Confirm Hardware
Config (Enter)
Confirm Config?
Yes No
Config Accepted
Enter to Reboot
COMMFLT
Warning
Save Changes?
Yes No