Specifications
Electrical Ratings
Main Circuits
825 Converter Module
MCM2
MCM5
MCM20
MCM180
MCM420
MCM630N
825-MCM Converter Modules
Rated Operating Voltage
U
e
—
400 V AC
240V AC
690V AC
600V AC
1,000V AC
600V AC
IEC:
CSA/UL:
Rated Impulse Strength
U
imp
2.5 kV
6 kV
8 kV
Operating Current Range (A)
0.5-2.5
1-5
2.5-20
20-180
160-420
160-630
Rated Continuous Thermal Current
(A)
3
6
24
216
504
756
Rated Saturation Current
30
60
240
1350
3400
4600
Rated Frequency
50/60 Hz ± 3 Hz
Voltage Input Option Card
Rated Operating Voltage
U
e
67…300V AC (line-to-line)
Operating Range
0.80…1.1
U
e
Rated Continuous Voltage
300V AC
Rated Insulation Voltage
U
i
300V AC
Rated Impulse Strength
U
imp
4 kV
Rated Frequency
50/60 Hz ± 5 Hz
Transition Voltage
5…15V
20…79V
PTC Thermistor Input
Type of Control Unit
Mark A
Max. No. of Sensors in Series
6
Max. Cold Resistance of PTC Sensor
Chain
1500
Ω
Trip Resistance
3400
Ω
± 150
Ω
Reset Resistance
1500
Ω
…
1650
Ω
Short Circuit Trip Resistance
25
Ω
±
10
Ω
Summary of Contents for 825-P
Page 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Page 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Page 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Page 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Page 265: ......