250
Rockwell Automation Publication 825-UM004D-EN-P - April 2012
Chapter E
DeviceNet Information
Standard Output
(Consumed) Assemblies
Instance 2 is the required output (consumed) assembly defined in the Motor
Overload Profile.
Instance 150 is the standard output (consumed) assembly with Network Inputs.
Instance 151 is the standard output (consumed) assembly with Network
Inputs.
This is a “Read/Write” control assembly.
Instance 3 ODVA Overload
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Flt Reset
Instance 150 Standard Consumed Starter
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Aux 8
Aux 7
Aux 6
Aux 5
Aux 4
Aux 3
Aux 2
Aux 1
1
Flt Reset
Aux 10
Aux 9
Instance 151 Standard Consumed Starter with Network Inputs
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Aux 8
Aux 7
Aux 6
Aux 5
Aux 4
Aux 3
Aux 2
Aux 1
1
Flt Reset
Aux 10
Aux 9
2
Net In 8
Net In 7
Net In 6
Net In 5
Net In 4
Net In 3
Net In 2
Net In 1
3
Net In 16
Net In 15
Net In 14
Net In 13
Net In 12
Net In 11
Net In 10
Net In 9
4
Net In 24
Net In 23
Net In 22
Net In 21
Net In 20
Net In 19
Net In 18
Net In 17
5
Net In 32
Net In 31
Net In 30
Net In 29
Net In 28
Net In 27
Net In 26
Net In 25
Instance 181 Hardware Outputs 1-6
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Aux 8
Aux 7
Aux 6
Aux 5
Aux 4
Aux 3
Aux 2
Aux 1
1
Flt Reset
Aux 10
Aux 9
Summary of Contents for 825-P
Page 1: ...Modular Protection System for Motors Catalog Number 825 P User Manual...
Page 4: ...4 Rockwell Automation Publication 825 UM004D EN P November...
Page 64: ...64 Rockwell Automation Publication825 UM004D EN P November 2012 Chapter 5 Using MPS Explorer...
Page 234: ...234 Rockwell Automation Publication 825 UM004D EN P April 2012 Chapter B ParameterList...
Page 265: ......