10
ArmorBlock MaXum 8 Input / 8 Output Module
Publication 1792D-5.20 - October 1998
For more information on indications see the Product Data publication
1792-2.1.
Network Status Indicator NS
Indication
Status
None
Not On-line
Green
Blinking
Solid
On-line/No Connections
On-line/Connected
Red
Solid
Failed Communication: A duplicate
node address exists or module is at the
wrong baud rate.
Auxiliary Power
Indication
Status
None
No Auxiliary Power
Green
Solid
Auxiliary Power Present
I/O Status Indicators
Function
Module Status Indicator
Point Indicator
1
Condition
Outputs
Green
Green
Module Status blink red
Module Status blink red
Module Status blink red
Module Status blink red
None
Yellow
Orange
Red
Orange
Red
Output not energized
Output energized
Output shorted-auto restart
Output shorted-latching
Output no load-auto restart
Output no load-latching
Inputs
Green
Green
Module Status blink red
Module Status blink red
None
Yellow
Red
Blink red
No valid input
Valid input
Short on input connector
1
Off wire on input connector
1
Only the first LED of each input connector will light as red when twin inputs are used.