background image

DIR 10005220601

(Version 03)

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.

For Technical Support, visit ROK.AUTO/SUPPORT.

 

Allen-Bradley, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1694-IN002D-EN-E -   June2020 

Copyright ©2020 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.

Rockwell Automation Support  

User Manual: Bulletin 1694 Electronic circuit protection for 24V DC

22

Rockwell Automation maintains current product environmental information on its website at: 

http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page

Installation Instructions, Manuals, Brochures, and Technical Data:

https://www.rockwellautomation.com/global/literature-library/overview.page

Bulletin 1694 web page:

https://rok.auto/1694-ECP

For the latest product information updates please check above links or www.rockwellautomation.com

       

Summary of Contents for Bulletin 1694

Page 1: ...l Only after expert installation must the device be supplied with power After tripping of the circuit protector and before reset the cause of the failure short circuit or overload must be remedied The...

Page 2: ...012s typically at IKS tKS 0 002s 1 see time current characteristics Rated current IN 1694 PM1 1 channel 1694 PM2 2 channel current ratings 1 A 2 A 3 A 4 A 6 A 8 A 10 A 1A 1A 2A 2A 3A 3A 4A 4A 6A 6A V...

Page 3: ...ltage was applied The device re starts with the last stored condition Reset function A blocked load output blocked by overload short circuit can be reset or switched on manually by the momentary ON OF...

Page 4: ...l be below 40 Amps sample case 36 channels refer to 1 Amp nominal current channels Dimensions h x w x d 12 5 x 80 x 98 5 mm Weight approx 60 g Conformity CE Marking RoHS compliant China RoHS WEEE Moro...

Page 5: ...ry max 80 of their rated load or a different rating has to be selected With high temperatures the load current warning threshold warn limit typically 0 9 x IN will be reduced in accordance with the te...

Page 6: ...n horizontal mounting position is preferred Publication 1694 IN002D EN E June 2020 DIR 10005220601 Version 03 User Manual Bulletin 1694 Electronic circuit protection for 24V DC 6 Marker 1 channel 2 ch...

Page 7: ...Circuit Protection Protection Module 1 Channel Fix Current In 1A Class 2 1694 PM12 Electronic Circuit Protection Protection Module 1 Channel Fix Current In 2A 1694 PM12 CL2 Electronic Circuit Protecti...

Page 8: ...ax 30 V no battery buffered applications Reverse polarity protection Yes without load Closed current I0 normal condition typically 10 mA min 6 5 mA max 11 8 mA Auxiliary contact potential free only in...

Page 9: ...e stripping length 5 Rockwell Automation recommends to use ferrules for smaller diameter cables 0 14mm2 to 2 5mm2 flexible AWG24 AWG14 str 5 8mm to 10mm Dimensions h x w x d 12 5 x 80 x 98 5 mm Weight...

Page 10: ...symbolic there is electrical connection between output and input connections for Line 1 and 0V done by semiconductor element Snap on socket for DIN rail EN 60715 35x7 5 CAT 1694 PF1244 SER X Allen Br...

Page 11: ...uit protection for 24V DC 11 0V LINE 1 COM ADDR LINE 1 0V View X View X CAT 1694 PF3L4C SER X Allen Bradley Power Feed 40A LC Contact arm snap on socket for DIN rail EN 60715 35x7 5 Marker 0V LINE 1 L...

Page 12: ...ircuit protection for 24V DC 12 View X View X CAT 1694 PF2L4S SER X Allen Bradley Power Feed 40A LS Contact arm snap on socket for DIN rail EN 60715 35x7 5 Marker 0V LINE 1 LINE 1 DC24V 40A 1694 PF2 V...

Page 13: ...2 5 2 4 2 3 2 2 2 1 2 10 2 9 2 8 2 7 2 6 0V LINE 1 COM ADDR View X CAT 1694 DM1L2 SER X Allen Bradley Distribution Load View without connector arm Contact arm snap on socket for DIN rail EN 60715 35x7...

Page 14: ...1694 DM2L2 SER X Allen Bradley Distribution Load View without connector arm Contact arm snap on socket for DIN rail EN 60715 35x7 5 Marker LOAD LOAD DC24V 20A 1694 DM2 2 5 2 4 2 9 2 4 2 9 2 3 2 8 2 3...

Page 15: ...symbolic there is electrical connection between output and input connections for Line 1 and 0V done by semiconductor element 1694 PF GND 1694 DM 1694 PF GND 0V View X CAT 1694 PF1G4 SER X Allen Bradl...

Page 16: ...M3G2 SER X Allen Bradley Distribution GND Contact arm snap on socket for DIN rail EN 60715 35x7 5 Marker 0V DC 0 24V 20A 1694 DM3 3 5 3 4 3 3 3 2 3 1 3 10 3 9 3 8 3 7 3 6 3 5 3 4 3 3 3 2 3 1 3 10 3 9...

Page 17: ...letin 1694 Electronic circuit protection for 24V DC 17 View X View X CAT 1694 PF3G4 SER X Allen Bradley Power Feed GND Contact arm snap on socket for DIN rail EN 60715 35x7 5 Marker 0V DC 0 24V 40A 16...

Page 18: ...er Feed Middle Mount Supply Voltage 24V DC Imax 40A LINE separated 1694 DM1L2 Distribution Module 10 Terminals 1xLINE 9xLOAD Imax 20A 1694 DM2L2 Distribution Module 10 Terminals 2xLINE separate 4xLOAD...

Page 19: ...on blade style screwdriver size 1 for smaller Push in terminal PT 2 5 inserts blade style screwdriver size 4 for larger Push in terminal PT 10 inserts Mounting position horizontal mounting position is...

Page 20: ...circuit protection for 24V DC 20 Caution Exchange disassembly only in dead voltage condition Potentials will be interrupted Unlatch with screwdriver Pull out at right angles to the rail Open connector...

Page 21: ...ctor arm of 1694 Application example 1694 installation area operating area User Manual Bulletin 1694 Electronic circuit protection for 24V DC 21 80 15 60 Contact arm Operating area Instalation area CA...

Page 22: ...omation Inc All Rights Reserved Printed in USA Rockwell Automation Support User Manual Bulletin 1694 Electronic circuit protection for 24V DC 22 Rockwell Automation maintains current product environme...

Reviews: