Rockwell Automation Publication 442G-DM001A-EN-P - September 2015

5

Multifunctional Access Box and Guard Locking with Time Delay Safety Relay

Four status indicators on the access box provide visual information about 

system status:.

Status/Diagnostic Indicators

Additional Features

Auxiliary/Manual Release

The auxiliary release lets you manually unlock the guard door in the event of 

unforeseen or uncommon circumstances. 

Note: 

When release monitoring is active (default factory setting), the system enters into a 

latching fault when the manual release is actuated. If the manual release is actuated too 
slowly, the system will not enter into a latching fault.

To reset the access box, turn the power off for at least three seconds or apply 

24V to the input RST for a minimum of three seconds. (In this demo, use the 

reset button next to the circuit breaker to the power supply.)

Note: 

You can reconfigure the access box DIP switches to deactivate Release 

Monitoring (refer to Chapter 4 – Change Device Configuration (use of DIP 

switches) in 442G-UM001A-EN-P).

Operating Mode

Status Indicator

State

Power (Green)

State (Green)

Diagnostic (Red)

Lock (Yellow)

Diagnostics

On

Green flash 1 time

On

Off

Error during handle configuration or invalid DIP switch setting

Green flash 2 times

Off

Input fault (only applies when switch is configured for series operation)

Green flash 3 times

Off

Handle module read error

Green flash 4 times

Off

Output fault

Off

Yellow flash 1x

Signal sequence erroneous or release has been actuated

Off

Off

Internal fault

Setup

Off

Off

Off

Positive acknowledgement after completion of handle configuration. 

Power cycle or device RESET are required to resume normal operation.

Normal Operation

Flashes green approximately 

every three seconds

Off

Off

Normal operation, door is open

IMPORTANT

The guard door must be in the open position to clear a latching fault. 

Summary of Contents for Guardmaster 442G-MABR-URM-C03

Page 1: ...Lock Request You press the Unlock Request button to request access to the safeguarded area The control system GLT relay shuts down the hazard and unlocks the guard door after a time delay Then you ar...

Page 2: ...800F Blue Push Button Reset GLT relay Relay Logic 2 Range 3 Time 6 SI Relay Automatic Manual Reset AM E stop Front View Rear View Escape Release A2 S12 S22 24 51 L61 B2 L12 L11 14 A1 S11 440R GL2S2T...

Page 3: ...gnals 5 Close the guard door The blue push button does not turn on again until you rotate the handle to insert the bolt into the lock module 6 To reset the safety system press the blue push button The...

Page 4: ...efault factory setting the system enters into a latchingfaultwhen the escape releaseis actuated If theescapereleaseis actuatedtooslowly the system will not enter into a latching fault 10 To reset the...

Page 5: ...to the circuit breaker to the power supply Note You can reconfigure the access box DIP switches to deactivate Release Monitoring refer to Chapter 4 Change Device Configuration use of DIP switches in 4...

Page 6: ...sms automatically extends when the handle is in the OPEN position The other mechanism is manually extended see Figure 1 To pivot out press the grooved part only possible with the handle in the OPEN po...

Page 7: ...Rockwell Automation Publication 442G DM001A EN P September 2015 7 Multifunctional Access Box and Guard Locking with Time Delay Safety Relay Notes...

Page 8: ...n com rockwellautomation about us sustainability ethics product environmental compliance page Allen Bradley and Guardmaster are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwe...

Reviews: