Rockwell Automation Publication 442G-DM001A-EN-P - September 2015
5
Multifunctional Access Box and Guard Locking with Time Delay Safety Relay
Four status indicators on the access box provide visual information about
system status:.
Status/Diagnostic Indicators
Additional Features
Auxiliary/Manual Release
The auxiliary release lets you manually unlock the guard door in the event of
unforeseen or uncommon circumstances.
Note:
When release monitoring is active (default factory setting), the system enters into a
latching fault when the manual release is actuated. If the manual release is actuated too
slowly, the system will not enter into a latching fault.
To reset the access box, turn the power off for at least three seconds or apply
24V to the input RST for a minimum of three seconds. (In this demo, use the
reset button next to the circuit breaker to the power supply.)
Note:
You can reconfigure the access box DIP switches to deactivate Release
Monitoring (refer to Chapter 4 – Change Device Configuration (use of DIP
switches) in 442G-UM001A-EN-P).
Operating Mode
Status Indicator
State
Power (Green)
State (Green)
Diagnostic (Red)
Lock (Yellow)
Diagnostics
On
Green flash 1 time
On
Off
Error during handle configuration or invalid DIP switch setting
Green flash 2 times
Off
Input fault (only applies when switch is configured for series operation)
Green flash 3 times
Off
Handle module read error
Green flash 4 times
Off
Output fault
Off
Yellow flash 1x
Signal sequence erroneous or release has been actuated
Off
Off
Internal fault
Setup
Off
Off
Off
Positive acknowledgement after completion of handle configuration.
Power cycle or device RESET are required to resume normal operation.
Normal Operation
Flashes green approximately
every three seconds
Off
Off
Normal operation, door is open
IMPORTANT
The guard door must be in the open position to clear a latching fault.