background image

Rockwell Automation Publication 20Y-IN004A-EN-P - October 2014

5

PowerFlex Active Front End in IP20 2500 MCC Style Enclosure Frame 13 Right-Side Bus Splice Kit

 

 

Step 5: Attach both enclosures using the air barrier panels and hardware 

supplied in the barrier kit (catalog number SK-Y1-MCCBARRIER).

a.

Note the air barrier panel orientations in this figure, position the 
barrier panels onto the right side of the AFE enclosure, and attach 
the panels using the supplied hardware (see table below).

 

b. Attach the right side of the AFE enclosure to the left side of the 

adjacent enclosure.
Torque fasteners to 55.0 in

lb (6.2 N

M) when fastening the 

enclosures together.

ATTENTION: 

The barrier kit must be used between the enclosures being 

attached together to maintain proper air flow within each individual enclosure. 
Failure to use the barrier kit can result in overheating that can cause equipment 
damage.

SK-Y1-MCCBARRIER Kit Supplied Parts/Hardware

Part Number

Quantity

PowerFlex 755 High HP Cabinet Barrier Panel, Rear

PN-204975

1

Cabinet Barrier Panel, Upper

PN-160374

(1)

(1) Only one barrier panel is required.

Cabinet Barrier Panel, Lower

PN-160385

(1)

Screw, Hex Flange HD, Taptite, M6 x 20 mm

29171-640-02

22

PN-204975

Upper Air Barrier Panel

PN-160374

DC+ Bus
Location

DC– Bus
Location

Lower Air Barrier Panel

PN-1603

8

5

Barrier Panels on Right Side of AFE Enclosure