Step 6: Connect the MCC bus and PE ground splices in the AFE enclosure to the bus 

and ground bars, respectively, in the other enclosure.

a.

Assemble the MCC bus splices to the horizontal bus bars in the 
other enclosure using the supplied hardware.
Torque to 300 ±10% in

lb (33.9 ±10% N

M).

b. Assemble the PE ground splices to the top and bottom PE ground 

bus bar connections in the other enclosure using the supplied 
hardware.
Torque to 65.0 ±10% in

lb (7.3 ±10% N

M) 

Adjacent Enclosure (Front View)

with Bus Bars to be Connected

to AFE Right-side Splices

AFE Enclosure

(Front View)