70
Rockwell Automation Publication 842E-UM001B-EN-P—April 2015
Appendix B
RSLogix 5000 sample code
3.
In the Configuration tab select:
Message type: CIP generic
Service type: Get attribute single
Service code: (automatically populated)
Source element: Preset_Value_Read (browse to this tag).
Instance: 1
Class: 23*
Attribute: 13*
* hexadecimal values
4.
In the Communication tab, browse to the encoder on the ethernet
network, then click OK.