4
31
WARNING
The washer-extractor should be connected to an individual branch
circuit not shared with lighting or other equipment.
Electrical Specifications HF150, IHF150, IHF033, CHF150, CHF033
150 liters / 33 pounds
Boiler Fed/Steam Heat
Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Recommended Circuit
Breaker (US-market)
AWG/mm2
kW Standard
Heating Elements
Full Load
Amps
Recommended
Circuit Breaker (US-
market)
AWG/mm2
US NON-US
US NON-US
N
440-480 50/60
3
3+PE
4,9 10
10
14/2.5
6x3 kW
29,6 40
32
12/4
P
380-415 50/60
3
3+N+PE 4,9 10
10
14/2.5
34,1 40
40
12/4
Q
200-240 50/60
3
3+PE
N/A N/A
N/A
N/A
52,8 50
63
10/6
X
200-240 50/60
1/3
2/3+PE
12
15
16
14/2.5
N/A N/A
N/A
N/A
Alternative Electric Heat Options
N
440-480 50/60
3
3+PE
6x2 kW
20,2 25
20
14/2.5
P
380-415 50/60
3
3+N+PE
23,2 30
25
14/2.5
Q
200-240 50/60
3
3+PE
36,3 40
40
12/4
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
N
440-480 50/60
3
3+PE
3x3 kW +
3x2 kW
24,9 30
25
14/2.5
P
380-415 50/60
3
3+N+PE
28,6 40
32
12/2.5
Q
200-240 50/60
3
3+PE
44,5 40
50
12/4
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
N
440-480 50/60
3
3+PE
3x3 kW +
3x4 kW
34,3 40
40
12/4
P
380-415 50/60
3
3+N+PE
39,5 50
40
12/4
Q
200-240 50/60
3
3+PE
N/A N/A
N/A
N/A
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
N
440-480 50/60
3
3+PE
6x4 kW
39
50
40
12/4
P
380-415 50/60
3
3+N+PE
47
60
50
10/6
Q
200-240 50/60
3
3+PE
N/A N/A
N/A
N/A
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
Table 3