24 kg/55 lb./240 L Models
Code
Voltage
(V)
Frequen-
cy (Hz)
Phase
Wire
Full Load
Amps (A)
Circuit
Breaker
CSA (A)
AWG
(mm
2
)
X
200-240
60
1/3
2 (L1, L2 or
L1, N)
15
20
12 (4)
N
440-480
60
3
3 (L1, L2, L3) 7.1
10
14 (2.5)
Table 33
28 kg/70 lb./280 L Models
Code
Voltage
(V)
Frequen-
cy (Hz)
Phase
Wire
Full Load
Amps (A)
Circuit
Breaker
CSA (A)
AWG
(mm
2
)
X
200-240
60
1/3
2 (L1, L2 or
L1, N)
16
20
12 (4)
N
440-480
60
3
3 (L1, L2, L3) 7.2
10
14 (2.5)
Table 34
Steam Requirements (Steam Heat
Option Only)
WARNING
Hot Surfaces. Will cause severe burns. Turn steam
off and allow steam pipes, connections and compo-
nents to cool before touching.
W505
For machines equipped with optional steam heat, install piping in
accordance with approved commercial steam practices. Steam re-
quirements are shown in
.
Specification
Requirement
Steam inlet connection size,
in. BSP
1/2"
Steam pressure, PSI [bar]
15-116 [1-8]
Table 35
IMPORTANT: It is necessary to insert a filter with per-
meability up to 0.0118 in. [300 µm] in front of the steam
valve. Dirt larger than 0.0118 in. [300 µm] may damage
the steam valve and cause leaks.
IMPORTANT: Failure to install the customer supplied
steam filter may void the warranty.
Use an inlet steam pressure hose only adapted to the steam valve
with appropriate seal suitable for the applied working pressure.
Steam Valve Installation
1. Remove the rear cover.
2. Fit the bracket with the steam valve and filter onto the rear
part of machine.