TMB2008N_SVG
3
2
4
5
2
1
1.
Lock
2.
Hose Couplings
3.
Y Valve
4.
Inlet Hoses
5.
Opening for Auxiliary Alarm Cable
Figure 5
Connect inlet hoses to water supply. Flush the lines for approxi-
mately two minutes to remove any foreign materials that could
clog the screens in the water mixing valve. This is especially im-
portant when installing a tumble dryer in a newly constructed or
renovated building. Then connect the hoses to the Y-valve; con-
nect the Y-valve to the connections at the rear of the tumble dry-
er.
IMPORTANT: Thread hose couplings onto valve con-
nections finger tight, then turn 1/4 turn with pliers. Do
not cross thread or overtighten couplings.
IMPORTANT: Hoses and other natural rubber parts de-
teriorate after extended use. Hoses may develop
cracks, blisters or material wear from the temperature
and constant high pressure they are subjected to. All
hoses should be checked on a yearly basis for any visi-
ble signs of deterioration. Any hose showing the signs
of deterioration listed above should be replaced imme-
diately. All hoses should be replaced every five years.
NOTE: Longer inlet hoses are available (as optional
equipment at extra cost) if the hoses supplied with the
tumble dryer are not long enough for installation. Order
hoses as follows:
Part No. 20617 Inlet hose 8 feet [2.44 m]
Part No. 20618 Inlet hose 10 feet [3.05 m]
NOTE: Replacement outlet hoses are available (at extra
cost). Order 44073301 Hose, 39 in. [99 cm ].
Electrical Requirements
WARNING
Electrical power must be provided to tumbler at all
times. The fire suppression system will be inopera-
tive if the main electrical power supply is discon-
nected.
W690
No independent external power source or supply connection is
necessary. Power to operate the 24 Volt fire suppression system
is from the rear junction/contactor box.
Auxiliary Alarm
The fire suppression system provides an auxiliary output signal
when the system is activated. During tumble dryer installation,
you have the option to connect a separate alarm system to this
auxiliary output. Potential uses of the auxiliary output include,
but are not limited to: (1) sounds an alarm, (2) activates a build-
ing sprinkler system, (3) notifies a fire department, etc. Use of the
auxiliary output is not required for the fire suppression system to
operate, but may be used for additional protection.
The connection to the auxiliary output is made through the FS-1
and FS-2 fast-on connections inside the fire suppression control
box. Refer to
Figure 6
. The relay is rated for 24 VAC, 5.2 Amp,
sealed current.
NOTE: The auxiliary output is activated during fire sup-
pression system maintenance test sequence. Consider
this fact prior to your system test every three months.
(Example: If the external system uses the auxiliary out-
put to call the fire department, inform the fire depart-
ment before and after the fire suppression system
maintenance test.)
Installation
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
25
Part No. 70457901ENR12
Summary of Contents for YU050E
Page 2: ......