Electrical Requirements
70458101 (EN)
46
Electrical Specifications
NOTE: Minimum wire sizes are obtained from
Canadian Electrical Code and are intended for use
as a guideline only. Electrical connections should be
made only by a qualified electrical contractor in
accordance with all applicable local and national
requirements.
NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only –
Each tumble dryer must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of “single
phasing” and causing premature failure of the
motor(s).
For 120 Series Gas and Steam Tumble Dryer Models
Serial Plate Rating
Terminal Block
Connections Required
Rated
Current*
(amps)
Breaker
Rating
Recommended Wire
Size mm² (AWG)
200-208/240V/60Hz/3ph
L1,L2,L3 and ground
7.7
15A - 3 pole
2.5 (14)
230V/50Hz/3ph
L1,L2,L3 and ground
7.3
15A - 3 pole
2.5 (14)
380V/50 or 60Hz/3ph
L1,L2,L3 and ground
4.1
10A - 3 pole
2.5 (14)
400-415V/50Hz/3ph
L1,L2,L3 and ground
3.8
10A - 3 pole
2.5 (14)
440V/60Hz/3ph
L1,L2,L3 and ground
3.8
10A - 3 pole
2.5 (14)
460-480V/60Hz/3ph
L1,L2,L3 and ground
3.9
10A - 3 pole
2.5 (14)
* Current ratings vary slightly depending on model; refer to serial plate.
Table 9
For 120 Series Electric Tumble Dryer Models
Serial Plate Rating
Terminal Block
Connections Required
Rated
Current*
(amps)
Breaker
Rating
Recommended Wire
Size mm² (AWG)
240V/60Hz/3ph
L1,L2,L3 and ground
152
175A - 3 pole
95 (3/0)
380V/50 or 60Hz/3ph
L1,L2,L3 and ground
94.5
125A - 3 pole
35 (1)
400-415V/50Hz/3ph
L1,L2,L3 and ground
87
125A - 3 pole
35 (1)
480V/60Hz/3ph
L1,L2,L3 and ground
76.1
100A - 3 pole
26.2 (3)
* Current ratings vary slightly depending on model; refer to serial plate.
Table 10
For 170 Series Tumble Dryer Models
Serial Plate Rating
Terminal Block
Connections Required
Rated
Current*
(amps)
Breaker
Rating
Recommended Wire
Size mm² (AWG)
200-208/240V/60Hz/3ph
L1,L2,L3 and ground
13.5
20A - 3 pole
4 (12)
380V/50 or 60Hz/3ph
L1,L2,L3 and ground
6.9
15A - 3 pole
2.5 (14)
400-415V/50Hz/3ph
L1,L2,L3 and ground
6.9
15A - 3 pole
2.5 (14)
440V/60Hz/3ph
L1,L2,L3 and ground
6.4
15A - 3 pole
2.5 (14)
460-480V/60Hz/3ph
L1,L2,L3 and ground
6.7
15A - 3 pole
2.5 (14)
* Current ratings vary slightly depending on model; refer to serial plate.
Table 11