508145-01

Page 28 of 36

Issue 2128

On-Board Link W951 Heat Pump (R to O)

On-board  link  W951  is  a  clippable  connection  between 

terminals R and O on the integrated control. W951 must 

be cut when the furnace is installed in applications which 

include a heat pump unit and a thermostat which features 

dual fuel use. If the link is left intact, terminal “O” will remain 

energized eliminating the HEAT MODE in the heat pump.

On-Board Link W915 2 Stage Compr (Y1 to Y2) 

On-board  link  W915  is  a  clippable  connection  between 

terminals Y1 and Y2 on the integrated control. W915 must 

be  cut  if  two-stage  cooling  will  be  used.  If  the Y1  to Y2 

link is not cut the outdoor unit will operate in second-stage 

cooling only.

Diagnostic Push Button

The diagnostic push button is located adjacent to the seven-

segment  diagnostic  LED.  This  button  is  used  to  enable 

the Error Code Recall “E” mode and the Flame Signal “F” 

mode. Press the button and hold it to cycle through a menu 

of  options.  Every  five  seconds  a  new  menu  item  will  be 

displayed. When the button is released, the displayed item 

will  be  selected.  Once  all  items  in  the  menu  have  been 

displayed, the menu resumes from the beginning until the 

button is released.

Unit Start-Up

FOR YOUR SAFETY, READ BEFORE LIGHTING UNIT

Do not use this furnace if any part has been underwater. 

A  flood-damaged  furnace  is  extremely  dangerous. 

Attempts to use the furnace can result in fire or explosion. 

Immediately call a qualified service technician to inspect 

the  furnace  and  to  replace  all  gas  controls,  control 

system parts, and electrical parts that have been wet or 

to replace the furnace, if deemed necessary.

 WARNING

If overheating occurs or if gas supply fails to shut off, 

shut off the manual gas valve to the appliance before 

shutting off electrical supply.

 WARNING

Before attempting to perform any service or 

maintenance, turn the electrical power to unit OFF at 

disconnect switch.

 CAUTION

BEFORE LIGHTING

 smell all around the appliance area 

for gas. Be sure to smell next to the floor because some 

gas is heavier than air and will settle on the floor.

The  gas  valve  on  this  unit  will  be  equipped  with  a  gas 

control  switch.  Use  only  your  hand  to  move  the  switch. 

Never use tools. If the switch will not turn or if the control 

switch will not move by hand, do not try to repair it.

Placing the Furnace into Operation

These  units  are  equipped  with  an  automatic  ignition 

system. Do not attempt to manually light burners on these 

furnaces.  Each  time  the  thermostat  calls  for  heat,  the 

burners will automatically light. The ignitor does not get hot 

when there is no call for heat on units with an automatic 

ignition system.

If  you  do  not  follow  these  instructions  exactly,  a  fire 

or  explosion  may  result  causing  property  damage, 

personal injury or death.

 WARNING

Gas Valve Operation

See Figure 24

1. 

STOP!

 Read the safety information at the beginning 

of this section.

2.  Set the thermostat to the lowest setting.
3.  Turn off all electrical power to the unit.
4.  This furnace is equipped with an ignition device which 

automatically lights the burners. Do not try to light the 

burners by hand.

5.  Remove the upper access panel.
6.  Move switch on gas valve to OFF. Do not force. See 

Figure 24.

7.  Wait  five  minutes  to  clear  out  any  gas.  If  you  then 

smell gas, 

STOP!

 Immediately call your gas supplier 

from  a  neighbor’s  phone.  Follow  the  gas  supplier’s 

instructions.

8.  Move switch on gas valve to ON. Do not force. See 

Figure 24.

9.  Replace the upper access panel.
10.  Turn on all electrical power to to the unit.
11.  Set the thermostat to desired setting.

NOTE: 

When unit is initially started, steps 1 through 

11 may need to be repeated to purge air from gas line.

12.  If the appliance will not operate, follow the instructions 

“Turning  Off  Gas  to  Unit”  and  call  your  service 

technician or gas supplier.

Summary of Contents for 80G2DFE

Page 1: ... agency or the gas supplier WARNING As with any mechanical equipment personal injury can result from contact with sharp sheet metal edges Be careful when you handle this equipment CAUTION Table of Contents 80G2DFE Gas Furnace 1 Unit Dimensions 2 Parts Arrangement 3 Shipping and Packing List 4 Safety Information 4 General 6 Combustion Dilution Ventilation Air 6 Downflow Installation 9 Filters 11 Du...

Page 2: ...W A B C D 3 4 19 27 3 4 705 19 1 4 489 6 5 8 168 Right 7 1 8 181 Left 5 3 8 137 Right 2 3 16 56 Left 33 838 AIR FLOW 3 4 19 19 7 16 494 9 16 14 B Supply Air Supply Air 9 16 14 9 16 14 3 1 8 79 9 16 14 9 16 14 19 7 16 494 3 4 19 Unit Dimensions Capacity A B C D in mm in mm in mm in mm 070A 12 14 1 2 368 13 3 8 340 13 330 4 3 4 121 090B 16 17 1 2 446 16 3 8 416 16 406 6 1 4 159 ...

Page 3: ...ts Arrangement Figure 1 Control Box includes integrated control transformer and door switch Secondary Limit Internal Flue Pipe Assembly Gas Valve Burner Box Assembly Combustion Air Inducer Indoor Blower Heat Exchanger Primary Limit Top Cap ...

Page 4: ...ional Fuel Gas Code ANSI Z223 1 The National Fuel Gas Code is available from the following address American National Standards Institute Inc 11 West 42nd Street New York NY 10036 Clearances Adequate clearance must be made around the air openings into the vestibule area In order to ensure proper unit operation combustion and ventilation air supply must be provided according to the current National ...

Page 5: ...DO NOT USE THE UNIT FOR CONSTRUCTION HEAT UNLESS ALL OF THE FOLLOWING CRITERIA ARE MET a Furnace must be in its final location The vent system must be permanently installed per these installation instructions b Furnace must be installed as a two pipe system and one hundred percent 100 outdoor air must be provided for combustion air requirements during construction c A room thermostat must control ...

Page 6: ... situation In the absence of local codes concerning air for combustion and ventilation use the guidelines and procedures in this section to install these furnaces to ensure efficient and safe operation You must consider combustion air needs and requirements for exhaust vents and gas piping A portion of this information has been reprinted with permission from the National Fuel Gas Code ANSI Z223 1 ...

Page 7: ...s a space categorized as unconfined air can be brought in by providing two permanent openings between the two spaces Each opening must have a minimum free area of 1 square inch 645 mm2 per 1 000 Btu 29 kW per hour of total input rating of all gas fired equipment in the confined space Each opening must be at least 100 square inches 64516 mm2 One opening shall be within 12 inches 305 mm of the top o...

Page 8: ...ve a free area of at least 1 square inch per 4 000 Btu 645 mm per 1 17 kW per hour of the total input rating of all other equipment in the enclosure Setting Equipment Do not install the furnace on its front or its back Do not connect the return air ducts to the back of the furnace Doing so will adversely affect the operation of the safety control devices which could result in personal injury or de...

Page 9: ...IR PLENUM OPENING Cabinet Width Front to Rear Side to Side in mm in mm A 14 1 2 19 3 4 502 13 1 4 337 B 17 1 2 19 3 4 502 16 1 4 413 NOTE Floor opening dimensions listed are 1 4 inch 6 mm larger than the unit opening See unit dimensions on Page 2 Table 1 Non Combustible Floor Opening Size Installation on Combustible Flooring Figure 9 1 When unit is installed on a combustible floor a downflow combu...

Page 10: ...al screws from the outside In this case make plenum with a removable front and install screws from the inside see Figure 12 5 Make certain that an adequate seal is made Cabinet Width Front to Rear Side to Side in mm in mm A 14 1 2 22 559 15 3 4 400 B 17 1 2 22 559 18 3 4 476 Table 2 Combustible Floor Opening Size Installation on Cooling Cabinet Figure 10 1 Refer to reverse flow coil installation i...

Page 11: ...ingle wall vent is used on 14 1 2 in cabinets or 2 in if a single wall vent is used on 17 1 2 in cabinets The furnace may be installed on a combustible wood floor if an optional additive base is installed between the furnace and the combustible floor Improper installation of the furnace can result in personal injury or death Combustion and flue products must never be allowed to enter the return ai...

Page 12: ...gas vent Unlined masonry chimneys are prohibited See Figure 17 and Figure 18 for common venting Venting Using a Masonry Chimney The following additional requirements apply when a lined masonry chimney is used to vent this furnace A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney An exterior masonry chimney that is not tile lined must b...

Page 13: ...himney no other appliance can be vented into the chimney The outer wall of type B1 vent pipe must not be exposed to flue products A type B1 vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof assembly according to the terms of their respective listings and the vent manufacturer s instructions When inspection reveals that an existing chimney is no...

Page 14: ...he maximum common vent capacity listed in the common venting tables should be reduced by 20 the equivalent of two 90 elbows 0 80 x maximum common vent capacity The horizontal length of the offset shall not exceed 1 1 2 feet 46 m for each inch 25 mm of common vent diameter 10 The vent pipe should be as short as possible with the least number of elbows and angles required to complete the job Route t...

Page 15: ... 49 39 98 51 164 64 247 10 0 0 88 0 175 0 295 0 447 2 12 61 17 118 23 194 26 289 5 23 57 32 113 41 187 52 280 10 30 51 41 104 54 176 67 267 15 0 0 94 0 191 0 327 0 502 2 11 69 15 136 20 226 22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 20 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 28 64 38 133 50 229 62 35...

Page 16: ... 220 15 1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 22 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 30 1 20 62 31 113 45 181 60 288 2 21 64 33 118 47 190 62 299 3 22 66 34 123 48 198 64 309 Table 6 Common Vent Capacity Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Applianc...

Page 17: ...ange hoods and bathroom exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Follow the lighting instructions Turn on the appliance that is being inspected Adjust the thermostat so that the appliance operates continuously 5 After the burners have operated for 5 minutes test for leaks of flue gases at the draft hood relief opening Use the flam...

Page 18: ... pressure drop Table 8 lists recommended pipe sizes for typical applications 3 The gas piping must not run in or through air ducts clothes chutes gas vents or chimneys dumb waiters or elevator shafts 4 The piping should be sloped 1 4 inch 6 4 mm per 15 feet 4 57 m upward toward the meter from the furnace The piping must be supported at proper intervals every 8 to 10 feet 2 44 to 3 01 m with suitab...

Page 19: ...e Size wiring and circuit breaker s per Technical Specification and unit rating plate CAUTION The unit is equipped with a field make up box on the left hand side of the cabinet The make up box may be moved to the right side of the furnace to facilitate installation If the make up box is moved to the right hand side clip the wire ties that bundle the wires together Secure the excess wire to the exi...

Page 20: ...d to one of the provided neutral terminals If a humidifier rated at greater than one amp is connected to this terminal it is necessary to use an external relay Generator Use Voltage Requirements The following requirements must be kept in mind when specifying a generator for use with this equipment The furnace requires 120 volts 10 Range 108 volts to 132 volts The furnace operates at 60 Hz 5 Range ...

Page 21: ...508145 01 Issue 2128 Page 21 of 36 070 12 090 16 COMFORT SYNC THERMOSTAT Figure 22 Wiring Diagram ...

Page 22: ...nd stage heat ON delay OFF 7 minutes ON 12 minutes ON CUT ON BOARD LINK W915 2 STAGE COMPR T STAT FURNACE TERM STRIP OUTDOOR UNIT Not required on all units 1 Heat 2 Cool with t stat with dehumidification mode NOTE Use DIP switch 2 to set sceond stage heat ON delay OFF 7 minutes ON 12 minutes ON CUT ON BOARD LINK W915 2 STAGE COMPR CUT ON BOARD LINK W914 DEHUM T STAT FURNACE TERM STRIP OUTDOOR UNIT...

Page 23: ... LINK W915 2 STAGE COMPR CUT ON BOARD LINK W914 T STAT FURNACE TERM STRIP OUTDOOR UNIT o Not required on all units 2 Heat 1 Cool with t stat with dehumidification mode OFF CUT ON BOARD LINK W914 T STAT FURNACE TERM STRIP OUTDOOR UNIT o Not required on all units 2 Heat 1 Cool OFF DO NOT CUT ANY ON BOARD LINKS T STAT FURNACE TERM STRIP OUTDOOR UNIT Not required on all units NOTE Do NOT make a wire c...

Page 24: ...URNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump Thermostat w dual fuel capabilities Capable of 2 stage gas heat control OFF CUT ON BOARD LINK W951 HEAT PUMP CUT ON BOARD LINK W915 2 STAGE COMPR FURNACE TERM STRIP HEAT PUMP out blue 67M41 H L Y2 D B L Y2 T T outdoor sensor T STAT Y2 NOTE Do NOT make a wire connection between the room thermostat L...

Page 25: ...NACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump Thermostat w dual fuel capabilities Capable of 2 stage gas heat control with dehumidification mode OFF CUT ON BOARD LINK W914 DEHUM CUT ON BOARD LINK W951 HEAT PUMP CUT ON BOARD LINK W915 2 STAGE COMPR T STAT FURNACE TERM STRIP HEAT PUMP 67M41 H L Y2 D B L Y2 T T outdoor sensor Y2 out blue Y2 NOTE Do...

Page 26: ...IGNAL Y2 THERMOSTAT 2ND STAGE COOL SIGNAL O THERMOSTAT SIGNAL TO HEAT PUMP REVERSING VA LVE L NOT USED DH NOT USED HUM UNPOWERED NORMALLY OPEN DRY CONTACTS LI 120 VAC INPUT TO CONTROL ACC 120 VAC OUTPUT TO OPTIONAL ACCESSORY NEUTRALS 120 VAC NEUTRAL 3 16 QUICK CONNECT TERMINALS FLAME SENSE SIGNAL HI Cool 24VAC HI HEAT 24VAC LO COOL 24VAC LO HEAT 24VAC PARK PARK COMMON 24VAC Flame Sense S4 DIP Swit...

Page 27: ... DIP Switch Settings Switches 3 and 4 Heating Mode Blower Off Delay The blower on delay of 30 seconds is not adjustable The blower off delay time that the blower operates after the heating demand has been satisfied can be adjusted by moving switches 3 and 4 on the integrated control The unit is shipped from the factory with a blower off delay of 90 seconds The blower off delay affects comfort and ...

Page 28: ...ore attempting to perform any service or maintenance turn the electrical power to unit OFF at disconnect switch CAUTION BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor The gas valve on this unit will be equipped with a gas control switch Use only your hand to move the switch Never use t...

Page 29: ...ial 1 cu ft Dial 2 cu ft Dial 070 55 110 136 272 090 41 82 102 204 Natural 1000 btu cu ft LP 2500 btu cu ft Table 13 Furnace should operate at least 5 minutes before checking gas flow Determine time in seconds for two revolutions of gas through the meter Two revolutions assures a more accurate time Divide by two and compare to time in Table 13 If manifold pressure matches Table 15 and rate is inco...

Page 30: ...ure in wg 4 501 7 500 ft Manifold Pressure in wg 7 501 10 000 ft 2 Supply Line Pressure in wg Low Fire High Fire Low Fire High Fire Low Fire High Fire Min Max 070 Natrual 1 7 3 5 1 5 3 2 1 7 3 5 4 5 13 0 LP Propane 3 4 5 10 0 4 5 10 0 4 5 10 0 11 0 13 0 090 Natrual 1 7 3 5 1 5 3 0 1 7 3 5 4 5 13 0 LP Propane 3 4 5 10 0 4 5 10 0 4 5 10 0 11 0 13 0 1 This is the only permissible derate for these uni...

Page 31: ...speed terminal 7 Resecure blower access panel 8 Turn on electrical power to furnace 9 Recheck temperature rise Heating Sequence of Operation Electronic Ignition The two stage variable speed integrated control used in 80G2DFE units has an added feature of an internal Watchguard control The feature serves as an automatic reset device for ignition control lockout caused by ignition failure After one ...

Page 32: ...h does not close the combustion air inducer will switch to high fire After a 15 second pre purge the high fire pressure switch will close and the unit will begin operation on high fire After 10 to 20 seconds of high fire operation the unit will switch to low fire 3 After the pre purge is complete a 20 second initial ignitor warm up period begins The combustion air inducer continues to operate at l...

Page 33: ...k for gas leaks CAUTION Annual Furnace Maintenance At the beginning of each heating season and to comply with the Allied Air Limited Warranty your system should be checked as follows 1 Check wiring for loose connections voltage at indoor unit and amperage of indoor motor 2 Check the condition of the belt and shaft bearings if applicable 3 Inspect all gas pipe and connections for leaks 4 Check the ...

Page 34: ...h Ignitor Primary limit control Flame rollout switch s Secondary limit Repair Parts List The following repair parts are available through independent Allied Air dealers When ordering parts include the complete furnace model number listed on the CSA International nameplate All service must be performed by a licensed professional HVAC installer or equivalent service agency or gas supplier Cabinet Pa...

Page 35: ...e in w c Air Volume Watts at Various Blower Speeds High Black Medium High Brown Medium Blue Medium Low Yellow Low Red cfm watts cfm watts cfm watts cfm watts cfm watts 0 10 1700 423 1495 293 1380 233 1295 202 1165 156 0 20 1665 436 1455 307 1330 248 1245 211 1110 166 0 30 1620 452 1415 319 1295 257 1195 221 1055 175 0 40 1585 464 1365 328 1225 269 1140 230 985 185 0 50 1560 471 1325 343 1185 277 1...

Page 36: ...m height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not app...

Reviews: