background image

507335-02

Page 33 of 39

Issue 2001

In the event the unit loses ignition, the control will attempt 

to  recycle  up  to  five  times  before  it  goes  into  a  1  hour 

lockout.  Lockout  may  be  manually  reset  by  removing 

power from the control for more than 1 second or removing 

the thermostat call for heat for more than 3 seconds.

If  during  a  heating  cycle  the  limit  control  senses  an 

abnormally high temperature and opens, the control board 

de-energizes  the  gas  valve  and  the  combustion  blower 

while  the  circulating  blower  ramps  up  to  2nd  stage  heat 

speed. The circulating blower remains energized until the 

limits are closed.

Fan On

When  the  thermostat  is  set  for  continuous  fan  operation 

and there is no demand for heating or cooling, a call for fan 

closes the R to G circuit and the circulating blower motor 

runs at 50% of the selected cooling CFM until switched off. 

When the call for fan is turned off, the control de-energizes 

the circulating blower.

Cooling

The unit is set up at the factory for single stage cooling. For 

two stage cooling operation, clip the jumper wire located 

between the Y to Y2 terminals on the integrated ignition/

blower control board.

If  the  active  dehumidification  feature  is  enabled,  the 

circulating  blower  runs  at  82%  of  the  selected  cooling 

speed as long as there is a call for dehumidification.

The system must not be in either the passive or active 

dehumidification mode when charging a cooling system.

 IMPORTANT

Single Stage Cooling

A  call  for  cooling  from  the  thermostat  closes  the  R  to Y 

circuit on the integrated ignition/blower control board. The 

control  waits  for  a  1-second  delay  before  energizing  the 

circulating  blower  to  82%  of  the  selected  cooling  CFM 

(passive  dehumidification  mode).  After  7.5  minutes,  the 

circulating  blower  automatically  ramps  up  to  100%  of 

the selected cooling  airflow. When the call for cooling  is 

satisfied, the circulating blower ramps back down to 82% 

of the selected cooling airflow for 1 minute, then shuts off.

Two Stage Cooling

A call for 1st stage cooling from the thermostat closes the 

R to Y circuit on the control board. The control waits for a 

1-second  delay  before  energizing  the  circulating  blower. 

The  blower  motor  runs  at  57%  of  the  selected  air  flow 

for the first 7.5 minutes of the 1st stage cooling demand 

(passive  dehumidification  mode).  After  7.5  minutes,  the 

blower motor runs at 70% of the selected cooling air flow 

until 1st stage cooling demand is satisfied.

A  call  for  2nd  stage  cooling  from  the  thermostat  closes 

the R to Y2 circuit on the control board. The blower motor 

ramps up to 100% of the selected cooling air flow. When 

the demand for cooling is met, the blower ramps down to 

Y1 until satisfied, then ramps down to 57% for 1 minute, 

then turns off.

Heat Pump

For  heat  pump  operation,  clip  the  jumper  wire  located 

below  the  O  terminal  on  the  integrated  ignition/blower 

control  board.  In  heat  pump  mode,  a  call  for  heat  will 

result in the circulating air blower operating at the selected 

cooling airflow after a brief ramp-up period. 

Emergency Replacement Motor Operation

If  the  variable  speed  motor  needs  to  be  replaced  in  an 

emergency  situation  (such  as  “no  heat”)  and  an  exact 

replacement motor is not immediately available, a standard 

PSC motor of equivalent frame size, voltage, rotation, and 

horsepower can be temporarily installed until the correct 

replacement motor can be obtained.

Connect the desired speed tap to the “EAC” terminal and 

the neutral tap to the neutral terminal on the ignition control 

(refer to the furnace wiring diagram). The ignition control 

will control the motor’s operation, including a nominal 20 

second “on” delay with a call for heat and a nominal 180 

second “off” delay when the thermostat is satisfied. It will 

also operate the motor on a call for cooling, with no “on” or 

“off” delays.

Verify that the unit is operating at the desired speed and 

within the rise range as shown on the unit rating plate.

The correct replacement motor must be installed as soon 

as possible to ensure continued satisfactory operation of 

the furnace.

Summary of Contents for 80G2UH070AV12

Page 1: ... installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a licensed professional installer or equivalent service agency or the gas supplier WARNING As with any mechanical equipment personal injury can result from contact with sharp sheet metal edges Be careful when you handle this equipment WA...

Page 2: ...eft 5 3 8 137 Right 1 9 16 40 Left 33 838 3 1 8 79 1 15 16 49 14 356 9 16 14 3 76 Right 6 3 4 171 Left 2 FLUE OUTLET Either Side 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Side 16 406 14 3 4 375 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Side 3 1 4 83 5 8 16 1 3 1 4 83 23 3 4 603 25 635 3 4 19 Front Panel AIR FLOW ELECTRICAL INLET Either Side Unit Dimensions Capacity A B C D ...

Page 3: ...TROL BOX BLOWER ASSEMBLY BURNER ACCESS PANEL BURNER BOX GAS VALVE COMBUSTION AIR INDUCER PRESSURE SWITCH COMBUSTION AIR INDUCER HEAT EXCHANGER CABINET BLOWER ACCESS PANEL INCLUDES INTEGRATED CONTROL AND TRANSFORMER ROLLOUT LOCATED INSIDE BURNER BOX Figure 1 ...

Page 4: ... current National Fuel Gas Code Vent installations must be consistent with the venting tables in this instruction and applicable provisions of local building codes This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the tables in Figure 8 and Figure 11 Installers should also consider the greater of either accessibil...

Page 5: ...heating is prohibited d The input rate and temperature rise must be set per the furnace rating plate e Supply and Return air ducts must be provided and sealed to the furnace Return air must be terminated outside of the space where furnace is installed f Return air temperature range between 60 F 16 C and 80 F 27 C must be maintained g MERV 11 or greater air filters must be installed in the system a...

Page 6: ...quire air for the combustion process If sufficient combustion air is not available the furnace or other appliances will operate inefficiently and unsafely Enough air must be provided to meet the needs of all fuel burning appliances and appliances such as exhaust fans which force air out of the house When fireplaces exhaust fans or clothes dryers are used at the same time as the furnace much more a...

Page 7: ...enclosure and one opening within 12 inches 305 mm of the bottom See Figure 3 Air from Outside If air from outside is brought in for combustion and ventilation the confined space must have two permanent openings One opening shall be within 12 inches 305 mm of the top of the enclosure and one opening within 12 inches 305 mm of the bottom These openings must communicate directly or by ducts with the ...

Page 8: ...back of the furnace Doing so will adversely affect the operation of the safety control devices which could result in personal injury or death WARNING The gas furnace can be installed as shipped in either the upflow position or the horizontal position Select a location that allows for the required clearances that are listed on the unit nameplate Also consider gas supply connections electrical suppl...

Page 9: ...and the platform to ensure that the furnace operates properly and safely The furnace is equipped with a removable bottom panel to facilitate installation Markings are provided on both sides of the furnace cabinet for installations that require side return air Cut the furnace cabinet at the maximum dimensions shown on Page 2 NOTE 20C and 20D units that require air volumes over 1800 cfm 850 L s must...

Page 10: ...ply and return air plenums must be supported separately NOTE When the furnace is installed on a platform in a crawlspace it must be elevated enough to avoid water damage and to allow the evaporator coil to drain Figure 12 Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets FRONT VIEW 1 Unit side return air Opening SIDE VIEW 3 1 4 83 1 23 584 Overall Maximum 584 23 3...

Page 11: ...The base must provide a stable support and an airtight seal to the furnace Allow absolutely no sagging cracks gaps etc The return and supply air duct systems must never be connected to or from other heating devices such as a fireplace or stove etc Fire explosion carbon monoxide poisoning personal injury and or property damage could result WARNING Filters This unit is not equipped with a filter or ...

Page 12: ...and the platform to ensure that the unit operates properly and safely Use fiberglass sealing strips caulking or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal If a filter is installed size the return air duct to fit the filter frame Venting A 4 inch diameter flue transition is factory installed on the combustion air inducer outlet of all models Figure 1...

Page 13: ...the pressure switch assembly Remove pressure switch assembly 1 screw and cut wire tie to free pressure switch wires Reinstall pressure switch on the other side of orifice plate and reconnect pressure switch hose Resecure pressure switch wires Either pull excess wires through the blower compartment and secure using supplied wire tie or coil excess wire and secure to the gas manifold Figure 20 Horiz...

Page 14: ...I Z223 1 and are provided as a guide for proper vent installation Proper application termination construction and location of vents must conform to local codes having jurisdiction In the absence of local codes the NFGC serves as the defining document Refer to the tables and the venting information contained in these instructions to properly size and install the venting system Once the venting syst...

Page 15: ...st first be lined with either type B1 vent or an insulated single wall flexible vent lining system which has been sized according to the provided venting tables and the vent pipe manufacturer s instructions IMPORTANT A fan assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met The chimney is currently serving at least one drafthood equipp...

Page 16: ...ommon venting Tables 5 6 7 and 8 were generated using a maximum horizontal vent connector length of 1 1 2 feet 46 m for each inch 25 mm of connector diameter as follows Table 2 Connector Diameter in mm Maximum Horizontal Connector Length ft m 3 76 4 1 2 1 37 4 102 6 1 83 5 127 7 1 2 2 29 6 152 9 2 74 7 178 10 1 2 3 20 11 If the common vertical vent is offset the maximum common vent capacity listed...

Page 17: ...g steps shall be followed for each appliance connected to the venting system being placed into operation while all other appliances connected to the venting system are not in operation 1 Seal any unused openings in the common venting system 2 Inspect the venting system for proper size and horizontal pitch Determine that there is no blockage restriction leakage corrosion or other deficiencies which...

Page 18: ... 15 136 20 226 22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 75 301 20 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 28 64 38 133 50 229 62 351 15 34 58 46 124 59 217 73 337 20 48 52 55 116 69 206 84 322 30 0 0 100 0 213 0 374 0 587 2 9 81 13 166 14 283 18 432 5 21 77 28 160 36 275 45 421 10 27 70 37 150 48 262 59 4...

Page 19: ...8 69 57 136 80 225 115 337 5 51 63 75 128 102 216 144 326 10 NR NR 95 116 128 201 182 308 15 NR NR NR NR 158 186 220 290 20 0 35 96 54 200 78 346 114 537 2 37 74 56 148 78 248 113 375 5 50 68 73 140 100 239 141 363 10 NR NR 93 129 125 223 177 344 15 NR NR NR NR 155 208 216 325 20 NR NR NR NR 186 192 254 306 30 0 34 99 53 211 76 372 110 584 2 37 80 55 164 76 281 109 429 5 49 74 72 157 98 271 136 41...

Page 20: ...92 52 146 69 220 15 1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 22 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 30 1 20 62 31 113 45 181 60 288 2 21 64 33 118 47 190 62 299 3 22 66 34 123 48 198 64 309 Common Vent Capacity Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Appl...

Page 21: ... 60 77 110 112 175 169 278 2 51 62 81 115 117 185 177 290 3 54 64 85 119 122 193 185 300 NOTE Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system For all other vent configurations the vent system is assumed to have two 90 elbows For each additional 90 elbow or equivalent for example two 45 elbows equal one 90 elbow beyond two the maxim...

Page 22: ...380 35 052 1400 39 64 950 26 90 770 21 80 660 18 69 580 16 42 530 15 01 490 13 87 460 13 03 430 12 18 400 11 33 1 1 2 38 1 1 610 40 894 2100 59 46 1460 41 34 1180 33 41 990 28 03 900 25 48 810 22 94 750 21 24 690 19 54 650 18 41 620 17 56 2 50 8 2 067 52 502 3950 111 85 2750 77 87 2200 62 30 1900 53 80 1680 47 57 1520 43 04 1400 39 64 1300 36 81 1220 34 55 1150 32 56 2 1 2 63 5 2 469 67 713 6300 1...

Page 23: ...LACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET Figure 26 Upflow Applications Possible Gas Piping Configurations GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE GROUND JOINT UNION DRIP LEG MANUAL MAIN SHUT OFF VALVE Horizontal Application Left Side Air Discharge Horizontal Application Right Side Air Discharge FIELD PROVIDED AND INSTA...

Page 24: ...es can be damaged if subjected to pressures greater than 1 2 psig 3 48 kPa 14 inches w c IMPORTANT Figure 28 Electrical ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostaticdischargecanaffectelectroniccomponents Take precautions during furnace installation and service to protect the furnace s electronic controls Precautions will help to avoid control exposure to electrostatic discha...

Page 25: ...th the neutral leg of the circuit being connected to one of the provided neutral terminals See Figure 43 for control configuration This terminal is energized in the heating mode whenever the combustion air inducer is operating 9 Install the room thermostat according to the instructions provided with the thermostat If the furnace is being matched with a heat pump refer to the instruction packaged w...

Page 26: ...s for heat See the furnace wiring diagram for specific connection information Electronic Air Cleaner Terminals are provided on the integrated ignition blower control board for connection of a 120 volt electronic air cleaner The EAC terminal is energized whenever the thermostat calls for heat cooling or continuous blower See furnace wiring diagram for specific connection information Variable Speed ...

Page 27: ...hes Each flash signifies 100 CFM count the flashes and multiply by 100 to determine the actual CFM delivered for example 10 flashes x 100 1000 CFM Adjust Tap Airflow amounts may be increased or decreased by 10 by moving the ADJUST jumper plug see Figure 32 from the NORM position to the or position Changes to the ADJUST tap will affect both cooling and heating airflows The TEST position on the ADJU...

Page 28: ...urn Air Heating CFM 0 through 0 8 w c Cooling CFM 0 through 0 8 w c Model Motor Hp Stage Speed Adjustment Heat Setting A Heat Setting B Heat Setting C Heat Setting D Cool Setting A Cool Setting B Cool Setting C Cool Setting D 80G2UH070AV12 1 2 2nd Norm 707 890 925 1013 926 1003 1104 1213 1st Norm 673 750 864 949 689 726 795 859 80G2UH090BV16 1 2nd Norm 1013 1075 1130 1394 897 1158 1346 1499 1st No...

Page 29: ...lve to the appliance before shutting off electrical supply WARNING Before attempting to perform any service or maintenance turn the electrical power to unit OFF at disconnect switch CAUTION During blower operation the ECM motor emits energy that may interfere with pacemaker operation Interference is reduced by both the sheet metal cabinet and distance WARNING BEFORE LIGHTING smell all around the a...

Page 30: ...e unit if service is to be performed 3 Remove the heating compartment access panel 4 Move gas valve switch to OFF position Do not force See Figure 33 and Figure 34 5 Replace the upper access panel Failure to Operate If the unit fails to operate check the following 1 Is the thermostat calling for heat 2 Are access panels securely in place 3 Is the main disconnect switch closed 4 Is there a blown fu...

Page 31: ...threaded plug on the inlet side of the gas valve provides access to the supply pressure tap Honeywell Valve 1 Remove the threaded plug 2 Install a field provided barbed fitting 3 Connect a manometer White Rodgers Valve 1 Loosen threaded plug removal not required 2 Connect a manometer See Table 15 for supply line pressure Replace or tighten the threaded plug after measurements have been taken Manif...

Page 32: ...re 35 through Figure 39 Heating On a call for heat from the room thermostat the control board performs a 1 second self check Upon confirmation that the pressure switch contacts are in an open position the control energizes the combustion blower on high speed The control then checks for adequate combustion air by making sure the low fire pressure switch contacts are closed The igniter energizes and...

Page 33: ...the selected cooling airflow for 1 minute then shuts off Two Stage Cooling A call for 1st stage cooling from the thermostat closes the R to Y circuit on the control board The control waits for a 1 second delay before energizing the circulating blower The blower motor runs at 57 of the selected air flow for the first 7 5 minutes of the 1st stage cooling demand passive dehumidification mode After 7 ...

Page 34: ...e W1 W2 Heat Call Figure 36 Indoor Blower Operation High Heat W2 Call Figure 37 Indoor Blower Operation Call for Fan Percentage of High Stage Cooling Figure 38 Indoor Blower Operation Single Stage Cooling Figure 39 Indoor Blower Operation Two Stage Cooling Percentage of High Stage Cooling ...

Page 35: ... further lubrication is needed The blower access panel must be securely in place when the blower and burners are operating Gas fumes which could contain carbon monoxide can be drawn into living space resulting in personal injury or death WARNING Filters All filters are installed external to the unit Filters should be inspected monthly Clean or replace the filters when necessary to ensure that the ...

Page 36: ... fault code is flashed last To clear the fault code history press and hold the pushbutton switch in for more than 5 seconds before releasing High Heat State LED On 80G2UH V models a green LED is provided on the control board to indicate high heat state see Table 18 CFM LED On 80G2UH V models equipped with a variable speed motor an amber LED is provided on the control board to display CFM To determ...

Page 37: ...ly shut down the furnace until the items can be repaired or replaced Instruct the homeowners to pay attention to their furnace Situations can arise between annual furnace inspections that may result in unsafe operation For instance items innocently stored next to the furnace may obstruct the combustion air supply This could cause incomplete combustion and the production of carbon monoxide gas Repa...

Page 38: ...507335 02 Page 38 of 39 Issue 2001 Figure 43 Typical Field Wiring Diagram ...

Page 39: ...507335 02 Page 39 of 39 Issue 2001 Figure 44 Wiring Schematic ...

Reviews: