508115-01
Issue 2043
Page 28 of 57
Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 − 10,000 ft.
Number
of 90
°
Elbows
Used
1-1/2” Pipe
2” Pipe
2-1/2” Pipe
3” Pipe
Capacity
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
045
070
090
110
1
20
15
n/a
n/a
61
46
24
n/a
100
80
43
n/a
127
127
108
108
2
15
10
56
41
19
95
75
38
122
122
103
103
3
10
n/a
51
36
14
90
70
33
117
117
98
98
4
n/a
46
31
n/a
85
65
28
112
112
93
93
5
41
26
80
60
23
107
107
88
88
6
36
21
75
55
18
102
102
83
83
7
31
16
70
50
13
97
97
78
78
8
26
11
65
45
n/a
92
92
73
73
9
21
n/a
60
40
87
87
68
68
10
16
55
35
82
82
63
63
Concentric Termination Elevation 0 − 10,000 ft.
Number
of 90
°
Elbows
Used
1-1/2” Pipe
2” Pipe
2-1/2” Pipe
3” Pipe
Capacity
Capacity
Capacity
Capacity
045
070
090
110
045
070
090
110
045
070
090
110
045
070
090
110
1
15
10
n/a
n/a
53
38
22
n/a
90
70
39
n/a
111
111
104
104
2
10
n/a
48
33
17
85
65
34
106
106
99
99
3
n/a
43
28
12
80
60
29
101
101
94
94
4
38
23
n/a
75
55
24
96
96
89
89
5
33
18
70
50
19
91
91
84
84
6
28
13
65
45
14
86
86
79
79
7
23
n/a
60
40
n/a
81
81
74
74
8
18
55
35
76
76
69
69
9
13
50
30
71
71
64
64
10
n/a
45
25
66
66
59
59
* Size intake and exhaust pipe length separately. Values in table are for intake or exhaust, not combined total. Both intake and
exhaust must be same pipe size.
Table 11.