5.
Using test jumpers, apply 24V to pins 3 and 4 on P49
on the motor.
NOTE:
Do not apply 24V to pins 2 and 4 on P49. Doing
so will cause permanent damage to the motor.
6. Motor should run at 75%.
7.
Test is complete. Remove jumpers and reconnect
plugs.
Another option is to use the TECMate PRO motor tester
with the 16 to 4 pin adaptor. The use of the TECMate PRO
isolates the motor from the integrated control. Follow the
instructions provided with the kit. If the motor runs, do not
replace.
Figure 8.
Blower B3 Harness Connectors
MOTOR with INTEGRATED
CONTROLLER
SHAFT
P49 4 Pin
P48 5 Pin
J48 5 Pin Line Voltage Connector
J49 4 Pin Control Connector
J48 5 Pin
J49 4 Pin
MOTOR with INTEGRATED
CONTROLLER
SHAFT
P49 4 Pin
P48 5 Pin
P48 5 Pin
P49 4 Pin
J48 Connector
installed on motor
P49 4 Pin
120v
0
240v
5
4
3
2
1
J48 Connector
24v Transformer
J49 Connector
Figure 9. Blower B3 Harness Connectors