508148-01
Issue 2128
Page 70 of 75
Program Unit Capacity Size Modes
Furnace
control
in IDLE mode (No
heating, cooling, or
indoor fan operation)
Turn room thermostat to OFF.
When the correct unit size code is displayed, release
button. Selected code will flash for 10-second period.
During that period, press and hold button for 5 seconds.
Integrated control will store code in memory and will
automatically exit
Program Unit Capacity/Size
mode
and reset. (If second period expires or button is held
less than 5 seconds, control will automatically exit
Program Unit Capacity/Size
mode and go into
Idle
mode without storing unit size code. If this happens,
programming function must be repeated.)
Verify that the selected unit size code is correct and
stored in non-volatile memory by cycling the 24 volt
power to the furnace control. (At 24 volt power-up of
the furnace control, the 7-segment LED will display
a unit size code. If three horizontal bars display, the
board does not recognize the unit size code. The
programming function must be repeated.)
FINISHED
Power-Up - Number displayed by integrated control represents unit size code (furnace
model and capacity). If three horizontal bars are displayed followed by continuous E203,
furnace control does not recognize unit size code. Configure per the following:
Yes
No
Push and hold button. Integrated control
will display unit size code number for
each furnace model for three seconds.
Solid
P
starts blinking on
7-segment LED.
P
To enter
Program
Unit Capacity/
Size
mode: Push
and hold button
next to 7-segment LED display until
solid “
P
” symbol appears. Release
button.
IMPORTANT
:
Field
replacement
controls may need to be manually
configured to validate furnace unit size
code.
P
UNIT
SIZE
CODE
FURNACE MODEL
UNIT
SIZE
CODE
FURNACE MODEL
0
A96US2V045B12S-01
6
A96US2V110C20S-01
1
A96US2V070B12S-01
7
A96US2V135D20S-01
2
A96US2V090C12S-01
8
A96DS2V045B12S-01
3
A96US2V090C16S-01
9
A96DS2V070B16S-01
4
A96US2V090C20S-01
11
A96DS2V090C20S-01
5
A96US2V110C16S-01
U
A96DS2V110C20S-01