507788-01
Issue 2007
Page 15 of 20
Blower Performance Data
Speed
Tap
Application
External Static Pressure (in. w.c.)
0.1
0.2
0.3
0.4
0.5
-24
1
Fan Only
590
575
530
480
430
2
Matched with 1.5 ton condensing unit
750
650
610
550
480
3
Nominal 2 ton match without electric heat
950
825
785
740
690
4
Nominal 2 ton match with electric heat
1040
1020
985
940
920
5
High static application
1160
1140
1120
1080
1050
-30
1
Fan Only
700
665
625
565
490
2
Matched with 2 ton condensing unit
860
810
770
715
665
3
Nominal 2.5 ton match without electric heat
1040
1010
980
940
890
4
Nominal 2.5 ton match with electric heat
1140
1100
1045
1015
980
5
High static application
1390
1375
1340
1285
1245
-36
1
Fan Only
850
800
750
665
600
2
Matched with 2.5 ton condensing unit
1080
950
910
850
775
3
Nominal 3 ton match without electric heat
1270
1230
1170
1120
1060
4
Nominal 3 ton match with electric heat
1440
1400
1330
1280
1240
5
High static application
1540
1475
1430
1380
1300
-42
1
Fan Only
990
915
860
810
725
2
Matched with 3 ton condensing unit
1190
1150
1100
1060
1020
3
Nominal 3.5 ton match without electric heat
1390
1350
1315
1280
1230
4
Nominal 3.5 ton match with electric heat
1665
1625
1585
1550
1510
5
High static application
1750
1710
1675
1640
1600
-48
1
Fan Only
1255
1210
1155
1115
1050
2
Matched with 3.5 ton condensing unit
1485
1450
1410
1365
1330
3
Nominal 4 ton match without electric heat
1720
1675
1630
1595
1550
4
Nominal 4 ton match with electric heat
1720
1675
1630
1595
1550
5
High static application
1840
1795
1755
1720
1680
-60
1
Fan Only
1100
1050
1000
925
830
2
Matched with 4 ton condensing unit
1625
1595
1565
1520
1490
3
Nominal 5 ton match without electric heat
1815
1780
1760
1730
1685
4
Nominal 5 ton match with electric heat
1900
1870
1835
1810
1765
5
High static application
1980
1955
1920
1890
1860
Table 4. BCE5E Constant Torque Air Handler Wet Air Flow Data