background image

506941-01

Page 9  of  16

Issue 1148

x

 

3600

 

x

= Cubic Feet Per Revolu

Ɵ

 on

BTU/HR
 INPUT

 # Seconds Per Revolu

Ɵ

 on

Hea

Ɵ

 ng

Value

To check this pressure:

1.  Turn off gas valve.

2.  Remove plug on valve marked “OUTLET PRESSURE.”

3.  Install a water manometer.

4.  Turn on gas valve and initiate a call for heat. If manifold 

pressure must be adjusted, remove cap from pressure 
regulator and turn adjustment screw clockwise to 
increase pressure or counterclockwise to reduce 
pressure.

5.  After checking pressure, turn gas off, remove manometer 

fi tting, and replace pipe plug and regulator cap.

6.  Put furnace in operation and check plug for leaks using 

soapy solution.

Burner and Burner Orifi ce Instructions

To check or change burners or burner orifi ces:

1.

  Close the main manual gas shutoff valve and turn 

off all power to unit.

2.  Remove the burner access panel. 

 

3.  Disconnect the union in the gas supply line upstream 

of the gas valve and downstream of the manual shutoff 
valve.

4.  Label wires going to the gas valve, then disconnect the 

wires.

5.  To change orifi ces:
 

a.  Remove 4 screws that fasten the manifold to the 
burner box assembly and remove the manifold.

 

b.  Remove the orifices, then install replacement 
orifi ces.

 

c.  To reassemble:  Reverse above steps, making 
sure orifi ces are inserted into the orifi ce holders on the 
back end of the burners, and that burners are level and 
centered on each burner opening in the vest panel.

6.  To remove or service burners:
 

a.  Label and disconnect the wires to the rollout switch 
and disconnect the igniter and fl ame sensor leads at 
the ignition control.

 

b.  Remove the 4 screws that secure the burner box 
assembly to the vest panel and remove the assembly 
from the unit.

 

c.  Remove the 6 screws that fasten the burner rack 
and bottom shield assembly to the burner box.  Burners 
are now accessible for removal.

 

d.  To Reassemble:  Reverse above steps.

Example:

 

The heating value of the gas is 1053 BTU/cubic 

foot.  By actual measurement, it takes 38 seconds for the 
hand on the 1-cubic foot dial to make a revolution with a 
100,000 BTU/HR furnace running. The result is 99,750 
BTU/HR, which is close to the 100,000 BTU/HR rating of 
the furnace.

Manifold Gas Pressure Adjustment Regulator – 
LPG/Propane Gas

LPG/propane units require a regulator, and a regulator on 
the LPG/propane tank is also required.

For purpose of input adjustment, the minimum 
permissible gas supply pressure (inlet side of gas valve) 
is 11” w.c. for LPG/propane.

If at any time ignition is slow and burner does not seem to 
be operating correctly, check manifold pressure (outlet side 
of the gas valve). 

It should be 10” to 10.5” w.c. pressure 

for LPG/propane.

The furnace is designed to obtain rated input at 10” w.c. 
manifold pressure for propane.

Manifold Gas Pressure Adjustment Regulator – Natural 
Gas

For purpose of input adjustment, the minimum permissible 
gas supply pressure is 5” w.c. for natural gas.
 

Gas input must never exceed the input capacity shown on 
the rating plate. 

 The furnace is equipped for natural gas 

rated inputs with manifold pressure of 3.5” w.c.

The manifold pressure can be measured by shutting off 
the gas, removing the pipe plug in the downstream side 
of the gas valve, and connecting a water manometer 
or gauge. 

Under no circumstances should the fi nal 

manifold pressure vary more than 0.3” w.c. from the 
above specifi ed pressures. 

 To adjust the regulator, turn 

the adjusting screw on the regulator clockwise to increase 
pressure and input or counterclockwise to decrease 
pressure and input.  See Figure 9 to assist in locating the 
regulator on the gas valve.

Check the furnace rate by observing the gas meter, making 
sure all other gas appliances are turned off.  The test hand 
on the meter should be timed for at least one revolution, 
noting the number of seconds per revolution.

 

 The heating 

value of the gas can be obtained from the local utility.

Summary of Contents for RGE Series

Page 1: ...d home application the ductwork must be sized to achieve static pressures within the manufacturer s guidelines All other installation guidelines must also be followed Failure to do so may result in equipment damage personal injury and improper performance of the unit WARNING Never use a flame to check for gas leaks Explosion causing injury or death may occur WARNING Do not store combustible materi...

Page 2: ...a forklift while still in the factory supplied packaging The lengths of the forks of the forklift must be a minimum of 42 Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident the extent of the damage should be noted on the carrier s freight bill A separate request for inspection by the carrier s agent should be made in writing Lo...

Page 3: ...f a roof curb is used follow the manufacturer s Installation Instructions and be sure that all required clearances are observed see Clearances section on this page This unit is shipped with four 4 corner brackets in place on the underside of the unit see Figure 1 All four 4 brackets must be removed before unit is installed onto roof curb assembly To avoid interference with roof curb remove the out...

Page 4: ...termined that each appliance remaining connected to the common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other fuel burning appliance to their previous condition of use 8 If improper venting is observed during any of the above tests the common venting system must be corrected See National Fuel Gas Code ANSI Z223 1 latest...

Page 5: ... Air Conditioning Contractors of America ACCA A closed return duct system shall be used This shall not preclude use of economizers or outdoor fresh air intake It is recommended that supply and return duct connections at the unit be made with flexible joints The supply and return air duct systems should be designed for the CFM and static requirements of the job They should not be sized by matching ...

Page 6: ...parate line and installed in accordance with all safety codes listed on page 1 After the gas connections have been completed open the main shutoff valve admitting normal gas pressure to the mains Check all joints for leaks with soapy solution or other material suitable for the purpose Never use a flame to check for gas leaks Explosion causing injury or death may occur WARNING The furnace must be i...

Page 7: ...most regulator manufacturers and LPG propane gas suppliers Check all connections for leaks when piping is completed using a soapy solution Some soaps used for leak detection are corrosive to certain metals Carefully rinse piping thoroughly after completing leak detection Electrical Wiring See Figures 6 7 All wiring should be done in accordance with the National Electrical Code ANSI NFPANo 70 lates...

Page 8: ... At no time should the standby gas pressure exceed 13 w c nor the operation pressure drop below 5 w c for natural gas units or 11 w c for propane gas If gas pressure is outside these limits contact the gas supplier for corrective action 4 Adjust temperature rise to be within the range specified on the raƟng plate To Light Main Burners 1 Turn off electrical power to unit 2 Turn the thermostat to lo...

Page 9: ... d To Reassemble Reverse above steps Example The heating value of the gas is 1053 BTU cubic foot By actual measurement it takes 38 seconds for the hand on the 1 cubic foot dial to make a revolution with a 100 000 BTU HR furnace running The result is 99 750 BTU HR which is close to the 100 000 BTU HR rating of the furnace Manifold Gas Pressure Adjustment Regulator LPG Propane Gas LPG propane units ...

Page 10: ...nnected open the main manual gas shutoff valve check for and correct any gas leaks Turn electrical power on initiate a call for heat and check for proper burner operation 8 Install burner access panel Heat Anticipator The heat anticipator setting is 0 75 amp It is important that the anticipator setpoint be correct Too high of a setting will result in longer heat cycles and a greater temperature sw...

Page 11: ...pre purge period 30 seconds nominal 3 When the pre purge period has expired the ignition control energizes the main gas valve and spark electrode for a period of 10 seconds 4 If the flame sensor does not sense that a flame has been established in the 10 second interval then the ignition control will de energize the gas valve and begins a 30 second interpurge period then initiates another trial for...

Page 12: ...box Carefully remove the flue collector box without ripping the adjacent insulation 4 Using a wire brush on a flexible wand brush out the inside of each heat exchanger from the burner inlet and flue outlet ends 5 Run the wire brush down the heat exchanger tubes from the burner end 6 Brush out the inside of the flue collector box 7 Clean the combustion air blower wheel and housing Run the wire brus...

Page 13: ...506941 01 Page 13 of 16 Issue 1148 CONNECTION DIAGRAM SINGLE STAGE HEAT 230 V 3 PHASE Figure 10 ...

Page 14: ...Page 14 of 16 506941 01 Issue 1148 CONNECTION DIAGRAM SINGLE STAGE HEAT 460 V 3 PHASE Figure 11 ...

Page 15: ... All applications Ten 10 years LF24 and TUA Stainless All applications Fifteen 15 years LD24 Aluminized All applications Two 2 years LD24 Stainless All applications Five 5 years LG14 All applications Five 5 years Burners LG14 Three 3 years Compressors 4SCU13LC 4SHP13LC Five 5 years TSA TPA Five 5 years KCA KGA KHA TCA TGA THA Five 5 years RGE13 RHP13 RCE13 Five 5 years NOTE If the date of original...

Page 16: ...omponents indoor unit outdoor unit and re frigerant control devices which do not match or meet the specifica tions recommended by the manufacturer e Operation of packaged gas electric units equipped with aluminized heat exchanger with mixed air temperatures of less than 45 F 7 C f Operation of furnaces with return air temperatures of less than 60 F 16 C or operation of a furnace field installed do...

Reviews: