English - 29 / 36
6-1622396 - rev. 3 - 21/09/2021
PARAMETER
DESCRIPTION
DEFAULT
CUSTOM
MIN
MAX
UM
23
deA
DEAD-MAN MODE:
0 = disabled
1 = enabled
0
0
1
24
SEr
Cycle threshold for assistance request. Once the threshold is
reached, the next cycles will be executed with fast flashing (if
Fpr
is active).
0 = disabled
0
0
100
x1000
cicli
25
SEf
Enabling continuous flashing for assistance request (function
performed only with closed automation):
0 = disabled
1 = enabled
0
0
1
26
SFt
Duration of the motor stop ramp, in case of immediate stop due
to alarms or protections. Not considered in case of wired STOP
command.
3
0
20
x100ms
27
EnP
Time of encoder.
7
4
80
ms
28
dEF
Setting the default values (RESET)
0
0
0
29
TRS
Display single transmitter memory position.
30
trC
Delete single transmitter.
31
trF
All radio memory erased. Enter to change the parameter and then
hold down the «MENU» key, a countdown appears and ends with
the word
don
.
32
SId
Not in use
1. SELECT INPUT DEVICE FOR OPENING
IAO
(0 – 4) default = 0
With this parameter you can select which photocell or loop controls the opening.
WARNING!
It is not possible to select PH3 or S3
for this function as they are reserved for detection of presence near the automation.
•
Value 0 = function disabled.
•
Value 1 = PH1 (photocell 1) command the opening.
•
Value 2 = PH2 (photocell 2) command the opening.
•
Value 3 = S1 (loop 1) command the opening.
•
Value 4 = S2 (loop 2) command the opening.
2. SELECT INPUT DEVICE FOR CLOSING
IAC
(0 – 5) default = 0
With this parameter you can select which photocell or loop controls the closing.
WARNING!
If PH3 or S3 are selected for this
function they, in addition to being able to control a closure on disengagement, will continue to function as security reversing the
motion in case of intervention during the closing of the bar.
•
Value 0 = function disabled.
•
Value 1 = PH1 (photocell 1) command the closing.
•
Value 2 = PH2 (photocell 2) command the closing.
•
Value 3 = S1 (loop 1) command the closing.
•
Value 4 = S2 (loop 2) command the closing.
•
Value 5 = PH3 and S3 (security photocell and loop near the automation) command the closing after the transit.
Summary of Contents for 12007336
Page 15: ...Italiano 15 36 6 1622396 rev 3 21 09 2021 45 45 1 2 3 1 2 3 FIG 27 FIG 28...
Page 51: ...English 15 36 6 1622396 rev 3 21 09 2021 45 45 1 2 3 1 2 3 FIG 27 FIG 28...
Page 87: ...Fran ais 15 36 6 1622396 rev 3 21 09 2021 45 45 1 2 3 1 2 3 FIG 27 FIG 28...
Page 123: ...Espa ol 15 36 6 1622396 rev 3 21 09 2021 45 45 1 2 3 1 2 3 FIG 27 FIG 28...
Page 159: ...Nederlandse 15 36 6 1622396 rev 3 21 09 2021 45 45 1 2 3 1 2 3 FIG 27 FIG 28...