INSTALLATION GUIDE
Telecontrol
TC-E
Packaging includes
-TC-E with battery, label versions for energy and volume
-Installation accessories (screws, peg, user seal)
-Installation Manual
2
4. Installation
Tools: screwdriver (type PZ1), approx. drill ø 6mm
4.1 Wall mounting (Picture 2)
The installation on the wall can be done by using a screw and wall plug
(ø 6mm, L=30mm) or as an alternative by sticking (e.g. using double-sided
tape).
•
Remove front cover screws and front cover.
•
Remove battery (in case of using screws and wall plug).
•
Install back cover on the wall.
4.2 Connecting the wires (Picture 3)
Cable diameters:
Cable ø 4–5.5mm: pull the cable through the cable insert (rubber part).
Cable ø 6.3mm: don’t use the cable insert.
•
Remove cable sleeve approx. 55 mm.
•
Strip insulation of single wires approx. 5mm.
•
Insert wires into holes inside PCB (terminals). Respect the polarity (e.g.
in case of open collector) !
•
Fix the terminal screws.
•
Place cable inside theTC-E
•
Replace the battery. Respect the polarity !
A display test starts. During the test 3 different pictures are displayed (each
picture displayed for 3s).
1
Generics
TC-E is a remote display for indexes of meters equipped with repetition output
(e.g. reed-switch or open collector). The pulse weight of TC-E and connected
meter must fit together (adjustment see 4.3).
In order to avoid any malfunction due to EMC the TC-E should not be installed
beside fluorescent lamps, electric motors, switch boxes or other sources of
electromagnetic influences. Don’t install signal lines in parallel to power lines.
Recommended minimum distance app. 0.5m.
CE sign
This product conforms to CE regulations (environmental class A according to
EN1434).
3
4
picture 1
picture 2
picture 3