ALLTRONIC GmbH, Raiffeisenstraße 11, 89438 Holzheim
Service-H49 9075 95 88 3-28
⚫
For 200/208/220/230/240VAC models:
The power cord is supplied in the UPS package.
⚫
For 100/110/115/120/127VAC models: The power cord is attached to the UPS. The input
plug is a NEMA 5-15P for 1K and 1.5K models, NEMA 5-20P for 2K model and NEMA 5-30P
for 3K model.
NOTE:
Check if the site wiring fault indicator lights up in LCD panel. It will be illuminated when
the UPS is plugged into an improperly wired utility power outlet (Refer to Troubleshooting
section). Please also check if there is a circuit breaker against overcurrent and short circuit
between the mains and AC input of the UPS for safety operation. The recommended protection
value as following:
⚫
For 200/208/220/230/240VAC models: 10A for the 1K and 1.5K models, 16A for the 2K
and 3K models.
⚫
For 100/110/115/120/127VAC models: 15A for the 1K and 1.5K models, 20A for 2K model
and 30A for 3K model.
Step 3: UPS output connection
There two kinds of outputs: programmable outlets and general outlets. Please connect
non-critical devices to the programmable outlets and critical devices to the general outlets.
During power failure, you may extend the backup time to critical devices by setting shorter
backup time for non-critical devices.
Step 4: Communication connection
Communication port:
USB port RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB/RS-232 port and the other to the communication
port of your PC. With the monitoring software installed, you can schedule UPS
shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When
installing either SNMP or AS400 card in the UPS, it will provide advanced communication and
monitoring options.
Step 5: Network connection
Network/Fax/Phone surge port
Connect a single modem/phone/fax line into surge-
protected “IN” o
utlet on the back panel of
the UPS unit. Connect from “OUT” outlet to the
equipment with another modem/fax/phone line
cable.
Step 6: Disable and enable EPO function
This UPS is equipped with EPO function. By default, the UPS is delivered from factory with Pin
1 and pin 2 closed (a metal plate is connected to Pin 1 and Pin2) for UPS normal operation. To
activate EPO function, remove two screws on EPO port and metal plate will be removed.
NOTE:
The EPO function logic can be set up via LCD setting. Please refer to program 16 in UPS
setting for the details.