04: ECO enable/disable
Parameter 1
Parameter 2
Interface
Setting
Enable or disable ECO function. You may choose the
following two options:
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)
⚫
05: ECO voltage range setting
Parameter 1
Parameter 2
Interface
Setting
Set the acceptable high voltage point and low voltage point
for ECO mode by pressing Down key or Up key.
HLS:
High loss voltage in ECO mode
in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
(Default: +12V)
For 100/110/115/120/127 VAC models, the setting range in
parameter 3 is from +3V to +12V of the nominal voltage.
(Default: +6V)
LLS:
Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage.
(Default: -12V)
For 100/110/115/120/127 VAC models, the setting voltage
in parameter 3 is from -3V to -12V of the nominal voltage.
(Default: -6V)
⚫
06: Bypass enable/disable when UPS is off
Parameter 1
Parameter 2
Interface
Setting
Enable or disable Bypass function. You may choose the
following two options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
⚫
07: Bypass voltage range setting
Parameter 1
Parameter 2
Interface
Setting
Set the acceptable high voltage point and acceptable low
voltage point for Bypass mode by pressing the Down key or
Up key.
HLS:
Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264:
setting the high voltage point in parameter 3
from 230Vac to 264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
120-140:
setting the high voltage point in parameter 3