15: Charger float voltage setting
Parameter 1
Parameter 2
Interface
Setting
Set up the charger float voltage.
2.20-2.33:
setting the charger float voltage from
2.20 V/cell to 2.33V/cell. (Default: 2.28V/cell)
⚫
16: EPO logic setting
Parameter 1
Parameter 2
Interface
Setting
Set up the EPO function control logic.
AO:
Active Open (Default). When AO is selected as EPO
logic, it will activate EPO function with Pin 1 and Pin 2 in
open status.
AC:
Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
⚫
17: External output isolation transformer connection
Parameter 1
Parameter 2
Interface
Setting
Allow or disallow external output isolation transformer
connection.
ENA:
If selected, it’s allowed to conne
ct to an external
output isolation transformer.
DIS:
If selected, it’s not allowed to connect to
external
output isolation transformer. (Default)
⚫
18: Display setting for autonomy time
Parameter 1
Parameter 2
Interface
Setting
Set up the display setting for autonomy time
EAT:
If EAT is selected, it will display the remaining
autonomy time. (Default)
RAT:
If RAT is selected, it will show accumulated autonomy
time so far.
⚫
19: Acceptable input voltage range setting
Parameter 1
Parameter 2
Interface
Setting
Set the acceptable high voltage point and acceptable low
voltage point for input voltage range by pressing the Down
key or Up key.
HLS:
Input high voltage point
For 200/208/220/230/240 VAC models:
280/290/300:
setting the high voltage point in parameter
2. (Default: 300Vac)
For 100/110/115/120/127 VAC models:
140/145/150:
setting the high voltage point in parameter
2. (Default: 150Vac)
LLS:
Bypass low voltage point