ANOMALY:
these are “minor” problems which reduce UPS performance or prevent certain functions from being used.
CODE
DESCRIPTION
A01
Incorrect data configuration
A03
Inverter not synchronized
A05
Overvoltage on Phase1 input line
A06
Overvoltage on Phase2 input line
A07
Overvoltage on Phase3 input line
A08
Undervoltage on Phase1 input line
A09
Undervoltage on Phase2 input line
A10
Undervoltage on Phase3 input line
A11
Input frequency out of tolerance range
A13
Voltage on Phase1 bypass line out of tolerance range
A14
Voltage on Phase2 bypass line out of tolerance range
A15
Voltage on Phase3 bypass line out of tolerance range
A16
Bypass frequency out of tolerance range
A18
Voltage on bypass line out of tolerance range
A22
Load on Phase1 > set user threshold
A23
Load on Phase2 > set user threshold
A24
Load on Phase3 > set user threshold
A25
Output switch open
A26
Positive battery branch absent or battery fuses open
A27
Negative battery branch absent or battery fuses open
A29
System temperature sensor fault
A30
System temperature < 0°C
A31
System overtemperature
A32
Phase1 dissipator temperature < 0°C
A33
Phase2 dissipator temperature < 0°C
A34
Phase3 dissipator temperature < 0°C
A36
Internal battery overtemperature
A37
External battery temperature sensor fault
A38
External battery overtemperature
A39
Positive branch batteries must be replaced
A40
Negative branch batteries must be replaced
// A47
Different firmware version
// =
Parallel Anomaly