16
C. Running current transformer tails
S O L S H A R E
X X X X X X
M1
M2
X X X X X X
X X X X X X
M3
X X X X X X
M4
X X X X X X
M5
M6
X X X X X X
X X X X X X
M7
X X X X X X
M10
X X X X X X
M8
X X X X X X
M9
Area of focus:
Conduit cable
D. Current transformers to SolShare connections
Wiring tails to Solshare:
1. Connect the CT cabling to the CT connector
block, as per the diagram to the right. To do this:
- Push the orange tab in and hold.
- Feed the CT cable into the hole.
- Once inserted, release the orange tab.
- Confirm cable is secure by giving it a gentle tug.
2. Repeat for all CT cables of the red phase.
3. Repeat steps 1 & 2 for white and blue phase
connector blocks.
4. Plug each CT connector block into the
corresponding socket of the SolShare.
Important:
Make sure colours and orientation of connectors
are identical to the image above. To ensure you are
positioning them correctly, check that the orange
tabs are above your plugged in cables, and labels
read as above.
1(L1)
3(L1)
5(L1)
7(L1)
9(L1)
2(L2)
2(L2)
1. Run CT conduit from Solshare to main switchboard. (CT
conduit gland is the largest gland on underside of SolShare)
2. Follow labels on current transformers and current transformer
tails. Ensure these match the corresponding unit.
3. Run tails of CTs from main switchboard to
SolShare through conduit.
Important:
Ensure labeling of head and tails of CT cables
as follows.