20
Connector options for both Code and Flex wire
2 hole copper compression connectors**, 1/4” stud hole with 5/8” spacing:
Panduit part series: LCD, LCC, LCC-W, LCD-W, LCDX, LCCF, LCCX
1 hole copper compression connectors**, 1/4 stud hole:
Panduit part series: LCAS, LCA, LCB, LCB-W, LCAX, LCAF, LCBX
Panduit anti-rotational copper mechanical connector:
Part #CLMAR/0-14-Q (#14AWG-2/0AWG)
Ferrules type:
FSD, F(12mm pin length recommended)
** 2 hole and 1 hole copper compression connectors available with short, standard, and long barrel lengths.
Bent tongue and narrow tongue options are available.
Diagram 3.
Appendix C – Terminal Block Connection
Connection data
Metric
US
Tightening Torque
2 Nm
18 lb-in
Conductor Cross Section Stranded min.
4 mm2
12 AWG
Conductor Cross Section Stranded max.
25 mm2
4 AWG
Conductor Cross Section Stranded with
Ferrule/Lug min.
4 mm2
Conductor Cross Section Stranded with
Ferrule/Lug max.
25 mm2
2 Conductors with same Cross Section
Stranded min
4 mm2
2 Conductors with same Cross Section
Stranded max
16 mm2
2 Conductors with same Cross Section
Stranded with TWIN Ferrule/Lug min.
4 mm2
2 Conductors with same Cross Section
Stranded with TWIN Ferrule/Lug max.
10 mm2
Stripping Length
14 mm
Internal Cylindrical Gauge
A8