Page 14 of 29
Your Smart Energy
Installation
sites with explosive atmosphere;
sites with direct sunlight;
sites with extreme change of ambient temperature;
wet rooms;
sites with highly flammable materials or gases; or
sites with a potentially explosive atmosphere;
Restricted Locations
The battery system shall
not be
installed —
(a) in restricted locations, as defined for switchboards in AS/NZS 3000;
(b) within 600 mm of any hot source, such as water unit, gas heater, air conditioning unit
or any other appliance.
(c) within 600 mm of any exit;
(d) within 600 mm of any window or ventilation opening;
(e) within 900 mm of access to 240 Vac connections;
(f) within 600 mm of side of other equipment.
A SMILE-BAT-G3-10.1P installed in any corridor, hallway, lobby or the like leading to a fire
exit shall ensure sufficient clearance from the SMILE-BAT-G3-10.1P for safe egress and
no less than 1 m.
A SMILE-BAT-G3-10.1P is considered a source of ignition and therefore shall not be
installed within hazardous area for gas cylinders containing heavier than air gasses and
gas relief vent terminal as defined in AS/NZS 3000.
Clearance for single battery has been displayed as following:
Clearance for battery system has been displayed as following: