47
Subject to technical amendments without prior notice | 83055400iUK – 2.1 | ait-deutschland GmbH
Parameter
Factory setting
Adjustment during
commissioning *)
Value range (adjustable steps) Access
low limit of applic.
L/W: device-dependent
LDWV: 62 °C
S/W & W/W: 52 °C
°C
35 °C – 75 °C (
↕
1)
AS
hysteresis cool.contr
L/W: 3.0 K
S/W: 2.0 K
1 K – 5.0 K (
↕
0.5) Fitter
service water max
65 °C
°C
30 °C – 65 °C (
↕
0.5) Fitter
min.systemtemp.
15 °C
°C
15 °C – 30°C (
↕
0.5)
User
Defrost end temperature
45 °C
35 °C – 45 °C (
↕
1)
LW161HAV / LW161HV : 35 °C – 50 °C (
↕
1)
AS
minimal flow mc 1
20 °C
°C
20 °C – 40 °C (
↕
1) Fitter
maximum flow mc 1
45 °C
°C
25 °C – 75 °C (
↕
1) Fitter
Hysteresis 2.CP short
4.0 K
K
2 – 6 (
↕
1) Fitter
desuperheater max.
65 °C
°C
30 °C – 75 °C (
↕
1) Fitter
min. flow cooling
18 °C
°C
18°C – 25 °C (
↕
1) Fitter
min. flow cooling 2CP
10 °C
°C
7 °C – 20 °C (
↕
1) Fitter
System settings
El. sup. blockade
no 2hg
no 2hg • with 2hg Fitter
Roomstat.
No
No • RBE • Smart
User
Integration
Return
Return • Sep. tank Fitter
Mixing circ 1
No
no • charge • discharge • cool • heat+cool Fitter
Error
no 2hg
no 2hg • Heating • DHW • with 2hg Fitter
Service water 1
sensor
sensor • Thermal
User
Service water 2
CP
CP • h.wCP Fitter
Service water 3
with CP
wo. CP • with CP Fitter
Service water 4
set value
set value • Max
Factory
Service water 5
device-dependent
wo HSP • with HSP • par HUP Fitter
SW+HP max
0 h
0 h – 8 h (
↕
0.5)
User
Defr cycle max
45 min
45 • 60 • 75 • 90 • 120 • 180 • 240 min Fitter
Defrost. Air
No
No • Yes
AS
Defr.Air max
15 min
5 min – 30 min (
↕
1)
AS
pump opt.
Yes
No • Yes
User
Access
AS
Fitter • AS
AS
brine pres/Flow
device-dependent
No • flow • Brine pres •
pow.suppl. • pow.+flow
AS
Control CP
On
Off • On
AS
setting hc
Set AT
Set AT • Fixed Tp Fitter
setting mc1
Set AT
Set AT • Fixed Tp Fitter
Cooling
Fixed Tp
Set AT • Fixed Tp
User
screed heating
w. mixer
wo. mixer • w. mixer
User
El. Anode
device-dependent
No • Yes
AS
Heating limit
Yes
No • Yes
User
parall. operation
No
No • Slave • Master Fitter
remote maintenance
No
No • Yes
User
pump optim. Time
180 min
5 – 180 min (
↕
5)
User
flow VBO
1 min
1 – 5 min (
↕
1) Fitter
min defrost cycle
45 min
45 • 60 • 90 • 120 • 180 • 240 • 300
Factory
time 2.CP short
20 min
5 – 20 min (
↕
1) Fitter
*) Please enter the adjusted values. Mark not applicable with — .