030-706-J0 Rev B
Page 22 of 26
7.4
Factory Ranges and Defaults
The following table lists the rectifier settings/ranges/defaults; changes are made via the CXC:
Setting
Range (minimum to maximum)
Default
Float (FL) Voltage
47.5 – 58.2V
54V
Equalize (EQ) Voltage
49.8 – 60.2V
55V
Battery Test (BT) Voltage
44 – 52V
46V
OVP
See note below – 63V
57V
Current Limit (CL)
23 – 100%
100%
Power Limit (PL)
0 – 100%
100%
Module Start Delay
0 – 250s
1s
System Start Delay
0 – 600s
0s
Low Voltage Alarm (LVA)
42 – 52V
44V
High Voltage Alarm (HVA)
52 – 63V
55.5V
EQ Timeout
1 – 2399h
30h
BT Timeout
1 – 250h
8h
Softstart Ramp-rate
Normal/Fast
Normal
CL/PL Alarm
Enable/Disable
Enable
Remote Shutdown
Enable/Disable
Enable
Ramp Test
Enable/Disable
Enable
Table F–Cordex 48-1kW rectifier factory ranges and defaults
NOTE:
OVP cannot be set below the present system/FL/EQ/BT voltage setting or the safe mode voltage of 51.4V.