0320008
‐
J0
Rev
B
Page
2
CAUTION
:
Risk
of
explosion
if
battery
is
replaced
by
an
incorrect
type.
Dispose
of
used
batteries
according
to
the
battery
manufacturer’s
instructions.
This battery pack is intended to be connected to an UPS. There will be a DC voltage at the connector
terminals.
Do not try to repair the unit yourself, contact your local supplier or your warranty will be void.
To eliminate any overheating of the battery pack, keep all ventilation openings free from obstruction and do
not place any foreign objects on top of the battery pack. Keep the battery pack 20 cm (8 in) away from the
wall.
Make sure the battery pack is installed within the proper environment as specified – ambient 0-40°C (32-
104°F) and 30-90% non-condensing humidity.
Do not install the battery pack under direct sunlight. Your warranty will be void if the batteries fail due to
overheating.
This battery pack is designed for indoor use only.
This battery pack is not designed for use in dusty, corrosive and salty environment.
The warranty for this battery pack will be void if water or other liquid is spilt or poured directly onto the battery
pack. Similarly we do not warrant any damage to the battery pack if foreign objects are deliberately or
accidentally inserted into the battery pack enclosure.
The battery will discharge naturally if the system is unused for a period of time. The batteries should be
charged by plugging in to a UPS for 12 hours every 6 months in a moderate climate (-5 to +30 °C / 23 to +86
°F), or every 3 months at higher temperatures (+30 to +45 °C / +86 to +113 °F). If this is not done, then the
warranty will be null and void.
During normal operation, the batteries will be automatically remained in charged condition.
When replacing batteries, always replace with the same quantity, type and capacity.
Summary of Contents for Alpha Continuity 10K
Page 1: ...Alpha Continuity 6K 10K Battery Pack User Manual Document 0320008 J0 Effective 04 2012 ...
Page 2: ......
Page 7: ...0320008 J0 Rev B Page 3 2 Rear Panel Components UPS Battery connector Electrical DC ...
Page 11: ...0320008 J0 Rev B Page 7 3 3 2 Rack Mount installation STEP 1 STEP 2 S3 B1 B2 S4 B1 B3 S4 ...
Page 15: ......