016-001-B0-002 6/97
3.1
APP60S Installation and Power Module Removal
POWER MODULES SHOULD BE SERVICED ONLY BY QUALIFIED PERSONNEL.
POWER MODULES CONTAIN MORE THAN ONE LIVE CIRCUIT. EVEN THOUGH AC IS
NOT PRESENT AT THE INPUT, IT MAY BE PRESENT AT THE OUTPUT.
Note: Before powering down a module, always switch the battery breaker OFF (or remove
the battery fuse) before removing AC, otherwise the module will transfer into inverter
operation.
Procedure
1.
Plug the APP60S "Jones" connector into the enclosure's SPI (Service Power Inserter).
2.
Plug the APP60S power cord into the enclosure's convenience outlet. Set the 30/60
VAC selector switch to the desired voltage and switch the APP60S ON.
3.
Toggle the SPI's "ALT/ON" switch to "ALT". This transfers output power from the module
to the APP60S which can now be used to maintain regulated, non-standby power to the
cable plant until a replacement power module has been installed.
4.
Switch the battery breaker on the power module OFF (or remove the battery fuse).
5.
Unplug the power module's LINE cord from the enclosure's convenience outlet.
6.
Wait approximately 1 minute for the power module's capacitors to fully discharge.
7.
Disconnect the wires from the side of the power module. CAUTION: Do not let exposed
battery cables come in contact with the chassis or enclosure.
8.
Remove the hold-down screw (AM Series modules only) and carefully slide the module
out of the enclosure. CAUTION: The ferroresonant transformer generates heat and may
cause burns if handled with bare hands.
9.
Reverse this procedure when re-installing a module. Note: Always test the power module
for proper operation before toggling the SPI's "ALT/ON" switch back to the "ON" position.
Plug the AC Line cord into
enclosure's convenience outlet
Plug the "Jones" connector into
Service Power Inserter's mating connector
Select required
output voltage
Switch the unit ON
3. INSTALLATION AND OPERATION
7
APP60S
Installation and Wiring