2. FEATURES
2.5 Communication / Interface Options,
continued
15
N.C.
Pin out: (RJ-45 connector, Female)
1.
LINE FAIL, COM contact
2.
LINE FAIL, N. C. contact
3.
LINE FAIL, N. O. contact
4.
LOW BATTERY, N. O. contacts
5.
LOW BATTERY, COM contacts
6.
LOW BATTERY, N. C. contacts
7.
8.
Low Battery
Warning
Line Failure
Line Present
N.C.
Battery OK
N.O.
Emergency UPS Shutdown
Switch (Wall Mounted).
NOTE: Cable length must not
exceed 100 feet. Use twisted
or shielded wire.
N.C. = Normally Closed
N.O. = Normally Open
External Alarms Connector Pin-out (with EPO Switch Option)
EPO
Emergency
Power OFF
Option
Pin out: (RJ-45 connector, centered key)
Pin 1
External Alarms Connector,
continued