21
3. INSTALLATION
3.2.1 Terminal Block Input and Output Wiring
, continued
* CAUTION: Refer to the nameplate voltage and frequency ratings affixed to the
unit. This power supply was wired for this particular voltage configuration when
it was shipped from the factory.
**Units shipped as 60Hz, single 120V output, do not use L2.
CFR 1500, CFR1500RM Terminal Block Output
Frequency
Voltages*
L1
N
L2**
60Hz
120 / 208VAC
120VAC
Neutral
208VAC
60Hz
120 / 240VAC
120VAC
Neutral
240VAC
50Hz
230 VAC
Not used
Neutral
230 VAC
CFR 1500, CFR 1500RM Terminal Block
Wire Guage and Tourque
MODEL
TERMINAL BLOCKS
TIGHTENING TORQUE
AWG
mm
2
Inch
Newton
Pounds
Meters
CFR 1500
CFR 1500 RM
14
2.0
35
4.0
Table 3.2.1
Table 3.2.3
WARNING: Overcurrent protection for the AC output circuit must be provided at
the time of installation.
CFR 1500, CFR 1500RM Terminal Block Input
Frequency
Voltage*
L
N
60Hz
120 VAC
120 VAC
Neutral
60Hz
208VAC
∅
1
∅
2
60Hz
240VAC
∅
1
∅
2
50Hz
230 VAC
230 VAC
N
e
u
t
r
a
l
Table 3.2.2
52
52
520
521
5.10 External Modem Parameters
External Modem setup:
This menu displays all the current external modem values. Refer
to each individual menu item for a detailed description.
Enable Automatic Alarms:
Y= Yes, N= No,
(Default value is “No”)
Setting “Enable Automatic Alarm” to “Yes” causes the modem to
dial out and report a problem whenever the specified power events (see
menu 522) happens. When enabling this feature, ensure that the Unsolicited
alarm feature (menu 509) is disabled. Always enable this feature near the
end of the modem configuration because CFR will try to communicate to
the modem two minutes after activating this feature.
Enable Remote Access:
Y= Yes, N= No,
(Default value is “No”)
Setting “Enable Remote Access” to “Yes” causes the CFR to set
the modem to answer remote calls on the first ring. Once a connection is
established, the remote host can access all CFR menus. The connection
exists until either the host drops the connection or the “Remote Hang Up
Time” expires (refer to menu 528). Enable this feature near the end of the
modem configuration because CFR would try to communicate to the
modem two minutes after activating this feature.
5. TERMINAL COMMUNICATION